background image

Instruction Manual

1. Marking

SMART Current Driver

HiC2031

ATEX certificate: CESI 06 ATEX 017

ATEX marking:

1

 II (1)G [Ex ia Ga] IIC

1

 II (1)D [Ex ia Da] IIIC

1

 I (M1) [Ex ia Ma] I

ATEX certificate: CESI 19 ATEX 027 X

ATEX marking: 

1

 II 3G Ex ec IIC T4 Gc

IECEx certificate: IECEx CES 06.0002X

IECEx marking:
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc

North America Certifcates: FM 19 US 0122 X , FM 19 CA 0065 X,
E106378 (UL)
Class I, Division 2, Groups A-D, T4
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups A-D; Class II Division 1, Groups E-G; Class III

Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc
Class I, Zone 2, Ex ec [ia Ga] IIC T4 Gc X

Fuchs Group

Lilienthalstraße 200, 68307 Mannheim, Germany

Internet: www.pepperl-fuchs.com

2. Target Group, Personnel

Responsibility for planning, assembly, commissioning, operation,
maintenance, and dismounting lies with the plant operator.
The personnel must be appropriately trained and qualified in order to carry
out mounting, installation, commissioning, operation, maintenance, and
dismounting of the device. The trained and qualified personnel must have
read and understood the instruction manual.
Prior to using the product make yourself familiar with it. Read the
instruction manual carefully.

3. Reference to Further Documentation

Observe laws, standards, and directives applicable to the intended use
and the operating location.
For mining applications, observe laws, standards, and directives
applicable to the operating location.
The corresponding datasheets, manuals, declarations of conformity, EU-
type examination certificates, certificates, and control drawings if
applicable supplement this document. You can find this information under
www.pepperl-fuchs.com.
Observe the instruction manuals for the associated termination boards.
If you use the device in safety-related applications, observe the
requirements for functional safety. You can find these requirements in the
functional safety documentation under www.pepperl-fuchs.com.

4. Intended Use

The device is only approved for appropriate and intended use. Ignoring
these instructions will void any warranty and absolve the manufacturer
from any liability.
The device is used in control and instrumentation technology
(C&I technology) for the galvanic isolation of signals such as 20 mA and
10 V standard signals or alternatively for adapting or standardizing signals.
The device has intrinsically safe circuits that are used for operating
intrinsically safe field devices in hazardous areas.

The device repeats the input signal from a control system to drive
HART I/P converters, valve actuators, and displays located in a
hazardous area.
Use the device only within the specified ambient and operating conditions.
Only use the device stationary.
Only use the module with the designated termination boards.
The device is an associated apparatus according to IEC/EN 60079-11.
The device is an electrical apparatus for hazardous areas of Zone 2.
The device may be installed in the non-hazardous area.
If you use the device in safety-related applications, observe the
information for safety function and safe state.

5. Improper Use

Protection of the personnel and the plant is not ensured if the device is not
used according to its intended use.

6. Mounting and Installation

Do not mount a damaged or polluted device.
Mount the device in a way that the device is protected against mechanical
hazard. Mount the device in a surrounding enclosure for example.
Mount the device with at least a degree of protection of IP20 according to
IEC/EN 60529.
The device must be installed and operated only in a controlled
environment that ensures a pollution degree 2 (or better) according to
IEC/EN 60664-1.
If used in areas with higher pollution degree, the device needs to be
protected accordingly.
Do not mount the device in the dust hazardous area.
The device must be installed and operated only in an environment of
overvoltage category II (or better) according to IEC/EN 60664-1.
Observe the installation instructions according to IEC/EN 60079-14.
If you install the device in safety-related applications, observe the
requirements for functional safety.

Requirements for Usage as Associated Apparatus

If circuits with type of protection Ex i are operated with non-intrinsically
safe circuits, they must no longer be used as circuits with type of
protection Ex i.
Observe the respective peak values of the field device and the associated
apparatus with regard to explosion protection when connecting intrinsically
safe field devices with intrinsically safe circuits of associated apparatus
(verification of intrinsic safety). Also observe IEC/EN 60079-14 and
IEC/EN 60079-25.
Keep the separation distances between all non-intrinsically safe circuits
and intrinsically safe circuits according to IEC/EN 60079-14.
Observe the compliance of the separation distances between two
adjacent intrinsically safe circuits according to IEC/EN 60079-14.

Requirements for Equipment Protection Level Gc

Only use the module in the hazardous area if the termination boards are
also approved for the hazardous area.
The device must be installed and operated only in surrounding enclosures
that

l

comply with the requirements for surrounding enclosures according to
IEC/EN 60079-0,

l

are rated with the degree of protection IP54 according to
IEC/EN 60529.

Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Only plug and pull the energized module in the absence of a potentially
explosive atmosphere.

Requirements for Division 2

Only use the module in the hazardous area if the termination boards are
also approved for the hazardous area.
The device must be installed and operated only in surrounding enclosures
that

l

comply with the requirements for surrounding enclosures according to
UL/CSA 60079-0,

l

are rated with the degree of protection IP54 according to
IEC/EN 60529.

Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Only plug and pull the energized module in the absence of a potentially
explosive atmosphere.

7. Operation, Maintenance, Repair

Do not use a damaged or polluted device.

Do not repair, modify, or manipulate the device.

If there is a defect, always replace the device with an original device.
If you operate the device in safety-related applications, observe the
requirements for functional safety. For the proof test, plan appropriate
intervals for the operation in low demand mode.

Requirements for Equipment Protection Level Gc

Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Only plug and pull the energized module in the absence of a potentially
explosive atmosphere.

Only use operating elements in the absence of a potentially explosive
atmosphere.

Requirements for Division 2

Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Only plug and pull the energized module in the absence of a potentially
explosive atmosphere.

DOCT-6488 / 2019-07

1 / 2

Reviews: