11 - 15
11 Adjustment Functions
G5-series Linear Motors/Servo Drives With Built-in EtherCAT Communications
11-4
Manu
al Tu
nin
g
11
11
-4-1
P
repar
ation f
or Manual Tu
ning
11-4 Manual Tuning
As described before, G5-series Servo Drives have a realtime autotuning function. However, there are
cases where realtime autotuning cannot adjust the gain properly due to restrictions such as load
conditions. Moreover, you may need to ensue optimum responsiveness and stability for each load.
Manual tuning is required in these situations.
This section describes how to perform manual tuning for each control mode and function.
More reliable adjustment can be performed quickly by using waveform monitoring with the data tracing
function of the CX-Drive or by measuring the analog voltage waveform with the monitor function.
The Motor Velocity Actual Value, Motor Velocity Demand Value, Force Command, and Following Error
Actual Value can be measured as an analog voltage level using an oscilloscope or other device.
The type of signal to output and the output voltage level are set with Analog Monitor 1 Selection
(3416 hex) and Analog Monitor 2 Selection (3418 hex) settings.
For details, refer to 11-1 Analog Monitor on page 11-2.
Commands to the motor and motor operation (speed, Force Command, and Following Error Actual
Value) can be displayed on a computer as waveforms.
Refer to the CX-Drive Operation Manual (Cat. No. W453).
11-4-1 Preparation for Manual Tuning
Analog Monitor Output
CX-Drive Data Tracing Function
USB communications cable
Connect to CN7.