Chapter
11 T
roubleshooting
11.3 Error List
11-63
ME0392-4C
Error
No.
Error name
Content and Cause /
Countermeasure
Co
ld
-st
art
629
Stroke parameter error
[Content & Cause]
1) Setting error in driver unit parameters
• The lead length acquired from the driver unit was 0 or less
• The soft limit + and - acquired from the driver unit are the same or
soft limit - is larger
[Countermeasure]
1) Check if the following setting in the parameter settings for the driver
unit is established correctly
• Lead length
• Positive side and negative side of soft limits
62A
Resolution related
parameter error
[Content & Cause]
1) Parameter setting error in driver unit
[Countermeasure]
1) Contact IAI
62B
Driver parameter data
error
[Content & Cause]
Parameter setting is inappropriate
1) Relation between Driver Unit Parameter No. 3 “Soft Limit Positive Side”
and Driver Unit Parameter No. 4 “Soft Limit Negative Side” is
inappropriate
[Countermeasure]
1) Set the values so it comes Soft limit positive side > Soft limit negative
side
62C
No operation output #
error
[Content & Cause]
1) A value other than an output number (other than from 0 to 6,999) was
input to the following parameters
• I/O Parameter No. 70 “Min. Non-Operated General Output Area
Number When All Axes / Programs Discontinued”
• I/O Parameter No. 71 “Max. Non-Operated General Output Area
Number When All Axes / Programs Discontinued”
• I/O Parameter No. 72 “Min. Non-Operated General Output Area
Number When All Axes Paused (Servo Axis Soft Int Output
Port Soft Interlock)”
• I/O Parameter No. 73 “Max. Non-Operated General Output Area
Number When All Axes Paused (Servo Axis Soft Int Output
Port Soft Interlock)”
[Countermeasure]
1) Input an output port number (from 0 to 6,999) to the following
parameters
• I/O Parameter No. 70 “Min. Non-Operated General Output Area
Number When All Axes / Programs Discontinued”
• I/O Parameter No. 71 “Max. Non-Operated General Output Area
Number When All Axes / Programs Discontinued”
• I/O Parameter No. 72 “Min. Non-Operated General Output Area
Number When All Axes Paused (Servo Axis Soft Int Output
Port Soft Interlock)”
• I/O Parameter No. 73 “Max. Non-Operated General Output Area
Number When All Axes Paused (Servo Axis Soft Int Output
Port Soft Interlock)”
Summary of Contents for R-unit RSEL
Page 2: ......
Page 5: ...ME0392 4C 2 Quick Start Guide Japanese Only ...
Page 32: ...Actuator Coordinate System Intro 18 ME0392 4C 2 Slider type 3 Table type 0 0 0 0 ...
Page 50: ...Chapter 1 RSEL System 1 4 Installation 1 13 ME0392 4C ...
Page 244: ...Chapter 4 Unit connection Installation and Wiring 4 5 PIO Circuit 4 32 ME0392 4C ...
Page 316: ...Chapter 5 Operation 5 10 ELECYLINDER Operation 5 52 ME0392 4C ...
Page 438: ...Chapter 6 Field Network PIO SIO 6 5 Example of Connectivity Setting 6 120 ME0392 4C ...
Page 532: ...10 6 Servo Gain Adjustment 10 90 10 7 Parameter Configuration Advanced Use 10 93 ...
Page 638: ...Chapter 10 Parameter 10 7 Parameter Configuration Advanced Use 10 106 ME0392 4C ...
Page 838: ...Chapter 14 Warranty 14 Warranty 14 3 ME0392 4C ...
Page 843: ......
Page 844: ......