Chapter 5 Operation
5.10 ELECYLINDER Operation
5-36
ME0392-4C
[4] Pressing complete output backward end/forward end (PE0/PE1) PLC input signal
● Turns ON when
“pressing complete” is determined during pressing operation.
● Turns OFF if no contact can be made.
[5] Alarm output (*ALM) PLC input signal
●
Turns ON when the ELECYLINDER is in normal status.
Turns OFF when an alarm occurs.
●
Always monitor the *ALM signal using the master device.
If it turns OFF, immediately take safety countermeasures with the equipment as a whole.
[6] Operation ready (E*RD) PLC input signal
●
It turns on when the operation is ready (servo on).
●
“*” = 0: 1st axis on EC connection unit ready for operation
1: 2nd axis on EC connection unit ready for operation
2: 3rd axis on EC connection unit ready for operation
3: 4th axis on EC connection unit ready for operation
Summary of Contents for R-unit RSEL
Page 2: ......
Page 5: ...ME0392 4C 2 Quick Start Guide Japanese Only ...
Page 32: ...Actuator Coordinate System Intro 18 ME0392 4C 2 Slider type 3 Table type 0 0 0 0 ...
Page 50: ...Chapter 1 RSEL System 1 4 Installation 1 13 ME0392 4C ...
Page 244: ...Chapter 4 Unit connection Installation and Wiring 4 5 PIO Circuit 4 32 ME0392 4C ...
Page 316: ...Chapter 5 Operation 5 10 ELECYLINDER Operation 5 52 ME0392 4C ...
Page 438: ...Chapter 6 Field Network PIO SIO 6 5 Example of Connectivity Setting 6 120 ME0392 4C ...
Page 532: ...10 6 Servo Gain Adjustment 10 90 10 7 Parameter Configuration Advanced Use 10 93 ...
Page 638: ...Chapter 10 Parameter 10 7 Parameter Configuration Advanced Use 10 106 ME0392 4C ...
Page 838: ...Chapter 14 Warranty 14 Warranty 14 3 ME0392 4C ...
Page 843: ......
Page 844: ......