Chapter 10 Parameter
10.5
Parameter List (ELECYLINDER)
10-82
ME0392-4C
10.5 Parameter List (ELECYLINDER)
10.5.1 Parameter list for ELECYLINDER
Shown below is a list of the parameters to ELECYLINDER.
No.
Name
Unit
Input range
Default setting
at shipping
Reference
Page
1
Operation range
adjustment
mm
0 to 9,999.69
Maximum stroke
10-83
2
Auto switch
“LS” signal
detection
range adjustment
mm Actuator Depended
to 9,999.99
0.10
10-84
3
Change home
return direction
-
Reverse, forward
According to
ELECYLINDER
specifications
10-85
4
Home position
adjustment
mm
0 to 9,999.99
According to
ELECYLINDER
specifications
10-86
5
Smooth
accel/decel
setting
-
Disabled,
enabled
Disabled
10-87
6
Current control
setting at stop
-
Disabled,
Powerful stop
Enabled,
Energy-saving
stop
Disabled
10-88
7
Wireless
function setting
-
Disabled,
enabled
Enabled
10-89
8
Power-saving
setting
-
Disabled,
enabled
Disabled
10-89
9
Select
Electromagnetic
Valve System
(Operation
System)
-
Double, Single
Double
(Not Available for
Change)
----
Caution
● No. 1/3/4 default factory settings differ according to ELECYLINDER specifications.
● No. 7 Wireless function setting parameter is not
displayed on ELECYLINDERs without
wireless circuit boards (no WL, WL2 in the Option model number).
● Do not attempt to change No. 9 Select Electromagnetic Valve System (Operation
System) parameter from Double.
10.5
Parameter List (ELECYLINDER)
ME0392-4C
10-83
10.5.2 Parameter details of ELECYLINDER
[Operation range adjustment (Parameter No. 1)]
No.
Name
Unit
Input range
Default initial value setting
1
Operation range
adjustment
mm
0 to 9,999.69
0
● The ELECYLINDER operation range can be adjusted to suit
your system.
● The minimum setting unit is 0.01
mm.
● Set to your desired stroke length.
The controller automatically adds 0.30 mm and controls/monitors the
operation range.
Set the operating stroke between 0 and 80 mm
by changing [Parameter No.1] to [80.00 mm].
Caution
● Set within the ELECYLINDER movable range.
Setting to a value that exceeds the maximum stroke will result in collision with the
forward side mechanical stopper
● This may damage the ELECYLINDER, workpiece or peripheral devices.
Configuration example
0.30 mm
0.30 mm
80.00 mm
(Stroke to be used)
Parameter No.1:
80.00 mm
ELECYLINDER only
Summary of Contents for R-unit RSEL
Page 2: ......
Page 5: ...ME0392 4C 2 Quick Start Guide Japanese Only ...
Page 32: ...Actuator Coordinate System Intro 18 ME0392 4C 2 Slider type 3 Table type 0 0 0 0 ...
Page 50: ...Chapter 1 RSEL System 1 4 Installation 1 13 ME0392 4C ...
Page 244: ...Chapter 4 Unit connection Installation and Wiring 4 5 PIO Circuit 4 32 ME0392 4C ...
Page 316: ...Chapter 5 Operation 5 10 ELECYLINDER Operation 5 52 ME0392 4C ...
Page 438: ...Chapter 6 Field Network PIO SIO 6 5 Example of Connectivity Setting 6 120 ME0392 4C ...
Page 532: ...10 6 Servo Gain Adjustment 10 90 10 7 Parameter Configuration Advanced Use 10 93 ...
Page 638: ...Chapter 10 Parameter 10 7 Parameter Configuration Advanced Use 10 106 ME0392 4C ...
Page 838: ...Chapter 14 Warranty 14 Warranty 14 3 ME0392 4C ...
Page 843: ......
Page 844: ......