Chapter
11 T
roubleshooting
11.3 Error List
11-61
ME0392-4C
Error
No.
Error name
Content and Cause /
Countermeasure
Co
ld
-st
art
622
Driver unit control power
voltage low
[Content & Cause]
1) Voltage error on 24V DC power supply
2) Malfunction on SEL unit
[Countermeasure]
1) Check the power voltage and replace the 24V DC power supply in case
of an error
2) Replace SEL unit
623
Coordinate system error
[Content & Cause]
1) The coordinate system definition data has been destroyed due to noise
being applied
2) Malfunction on SEL unit
[Countermeasure]
1)-1 Initialize the coordinate system definition data
1)-2 Take a counteraction against noise on the controller (if happens
often)
2) Replace SEL unit
624
Simple interference
check zone error
[Content & Cause]
1) A value as shown below was indicated to the zone irruption output
number (indicated in the simple interference check zone edit window in
SOIF Command, PC software and TP) for the simple interference
check zone;
• A value other than the output port or global flag number (0 is
acceptable)
• A number duplicated with the output number indicated in the system
output (such as output feature select, linear axis zone, etc.)
2) A simple interference check zone number out of the range (other than
from 1 to 10) was indicated in a SEL command
[Countermeasure]
1) Check the zone irruption output number for the simple interference
zone and indicate a value following those below;
• Output port
• Indicate a global flag number or 0
• Avoid indicating an output port indicated in the system output
2) Check the simple interference check zone number indicated in the
program step that the error occurred and indicate a value in the range
available for input
625
Multi-slider parameter
error
[Content & Cause]
1) Setting error in Axis Parameter No. 41 “Multiple Slider Excess
Approach Detection Target Axis Indication”
• An inappropriate axis number was indicated
• Two slider axis numbers mutual indication error
• A next axis number physically impossible considering the structure of
the linear axes was indicated
• A synchronized slave number indicated
[Countermeasure]
1) Check the setting in Axis Parameter No. 41 “Multiple Slider Excess
Approach Detection Target Axis Indication” and revise it
Summary of Contents for R-unit RSEL
Page 2: ......
Page 5: ...ME0392 4C 2 Quick Start Guide Japanese Only ...
Page 32: ...Actuator Coordinate System Intro 18 ME0392 4C 2 Slider type 3 Table type 0 0 0 0 ...
Page 50: ...Chapter 1 RSEL System 1 4 Installation 1 13 ME0392 4C ...
Page 244: ...Chapter 4 Unit connection Installation and Wiring 4 5 PIO Circuit 4 32 ME0392 4C ...
Page 316: ...Chapter 5 Operation 5 10 ELECYLINDER Operation 5 52 ME0392 4C ...
Page 438: ...Chapter 6 Field Network PIO SIO 6 5 Example of Connectivity Setting 6 120 ME0392 4C ...
Page 532: ...10 6 Servo Gain Adjustment 10 90 10 7 Parameter Configuration Advanced Use 10 93 ...
Page 638: ...Chapter 10 Parameter 10 7 Parameter Configuration Advanced Use 10 106 ME0392 4C ...
Page 838: ...Chapter 14 Warranty 14 Warranty 14 3 ME0392 4C ...
Page 843: ......
Page 844: ......