Chapter 5 Operation
5.10 ELECYLINDER Operation
5-34
ME0392-4C
The input and output signals for the EC connection unit are as shown below.
On means the applicable bit is "1" while off means "0".
[1] Movement command input backward end/forward end (ST0/ST1) PLC output signal
The ST signal function automatically switches depending on whether the unit has completed
home return or not.
Signal name
Signal
abbreviation
Function overview by status
Home return:
Not complete
Home return: Complete
Backward
ST0
Home return operation
Backward
Forward
ST1
Forward
[Home return status: Not complete]
●
When the “ST0” signal is turned ON, home return operation begins.
●
When the “ST1” signal is turned ON, as with the “ST0” signal, home return operation begins.
●
Turning the ST signal OFF midway through home return operation will cause a gradual stop.
[Home return status: complete]
● When the ST signal is turned ON, the ELECYLINDER moves “Backward” or “Forward”.
● While the ST signal is ON, operation will continue until the “Backward end” or “Forward end”
is reached.
● Turning the ST signal OFF midway through operation will cause a gradual stop.
Caution
●
If stopped when the LS or PE signals are not ON, the ELECYLINDER may be stopped
on the way to the backward or forward end, or it may have stopped at the backward or
forward end during pressing operation with no contact.
We recommend first inputting the “ST0” signal and then performing the following actions
after returning to the backward end.
●
If battery-less absolute specification (option) is selected, the home return complete status
is retained.
However, if the “Change home return direction” or “Adjust home position” parameters are
changed, home return status will be not-complete; perform homing (absolute reset).
●
ELECYLINDER connected to RSEL is not capable for use in the single solenoid system.
Summary of Contents for R-unit RSEL
Page 2: ......
Page 5: ...ME0392 4C 2 Quick Start Guide Japanese Only ...
Page 32: ...Actuator Coordinate System Intro 18 ME0392 4C 2 Slider type 3 Table type 0 0 0 0 ...
Page 50: ...Chapter 1 RSEL System 1 4 Installation 1 13 ME0392 4C ...
Page 244: ...Chapter 4 Unit connection Installation and Wiring 4 5 PIO Circuit 4 32 ME0392 4C ...
Page 316: ...Chapter 5 Operation 5 10 ELECYLINDER Operation 5 52 ME0392 4C ...
Page 438: ...Chapter 6 Field Network PIO SIO 6 5 Example of Connectivity Setting 6 120 ME0392 4C ...
Page 532: ...10 6 Servo Gain Adjustment 10 90 10 7 Parameter Configuration Advanced Use 10 93 ...
Page 638: ...Chapter 10 Parameter 10 7 Parameter Configuration Advanced Use 10 106 ME0392 4C ...
Page 838: ...Chapter 14 Warranty 14 Warranty 14 3 ME0392 4C ...
Page 843: ......
Page 844: ......