Chapter 6 Field Network, PIO, SIO
6.3 Parameter Configuration
6-88
ME0392-4C
PROFIBUS-DP + PIO
●
Example of Use (1)
It is the setting when PROFIBUS-DP is to be used for 256 points of each input and output
from the top of the extension input and output ports (No. 1,000 ~, No. 4,000 ~), and PIO is to
be used for 48 points of each input and output from the top of the input and output ports (No.
0 ~, No. 300 ~).
In this case, three units of PIO units (16 points x 3 units = 48 points) should be used.
No.
Parameter Name
Setting at
Delivery
Set
Value
Unit
Remarks
1
I/O port assignment type
0
0
0: Fixed assignment
1: Automatic assignment
14
Number of Ports Used for
I/O1 Fieldbus Remote Input
64
256
Multiple of 8
15
Number of Ports Used for
I/O1 Fieldbus Remote Output
64
256
Multiple of 8
16
I/O1 fix-allocated input port
start No.
0
1,000
0 + (Multiple of 8) (0 to 299)
1,000 + (Multiple of 8) (1,000 to 3,999)
(Invalid if a negative value is set.)
17
I/O1 fix-allocated output port
start No.
300
4,000
300 + (multiple of 8) (300 to 599)
4,000 + (multiple of 8) (4,000 to 6,999)
(Invalid if a negative value is set.)
18
I/O1 error monitor
1
1
0: Do not monitor
1: Monitor
* Some exceptions apply.
20
Input filtering periods
2
Optional msec
Input signal is recognized when the status is
held for twice the period set by this parameter.
* Valid only for PIO, PIO unit /
PIO/SIO unit
120 Network attribute 1
64
1
001H
Optional
Bits 4-11: I/O1 Fieldbus link error
confirmation timer value (10 ms)
Bits 28-31: Input Port Data Select in I/O1 Fieldbus
Link Error (0: Clear, 1: Hold)
121 Network attribute 2
C80000H
Optional
Bits 16-27: Link timeout value in Fieldbus
initialization (100 ms)
186
Number of Connected option
unit
0
3
unit
The number of ports used for input and output
should be number of connected units * 16 for each.
187
Option unit fix-allocated input
port start No.
-1
0
0 + (Multiple of 8) (0 to 299)
1,000 + (Multiple of 8) (1,000 to 3,999)
(Invalid if a negative value is set)
188
Option unit fix-allocated
output port start No.
-1
300
300 + (Multiple of 8) (300 to 599)
4,000 + (Multiple of 8) (4,000 to 6,999)
(Invalid if a negative value is set)
Extension input port No.1,000 to 1,256
Extension output port No.4,000 to 4,256
Input port No.0 to 47
Output port No.300 to 347
6.3 Parameter Configuration
ME0392-4C
6-89
No.
Parameter Name
Setting at
Delivery
Set
Value
Unit
Remarks
189 PIO Unit / PIO/SIO Unit Error
Monitor
1
1
0: Not monitored
1: Monitored
2: Monitored (24V I/O power supply related errors
not monitored)
3: Monitored (only 24V I/O power supply related
errors monitored)
4: Monitored (24V I/O power supply related errors
output as message level)
* Some exceptions apply
190 Option Unit Attribute 1
C800200H Optional
Bits 0 to 3: PIO unit output port data select in TF
connection error (0: Clear, 1: Hold)
Bits 4 to 7: PIO unit input port data select in TF
connection error (0: Clear, 1: Hold)
Bits 8 to 15: TF communication link error check timer
value (10ms)
Bits 20 to 31: Link timeout value in TF
communication initialization (100ms)
225 I/O controller
3H
3H
Bits 0-7: Type of Network I/F Module Control 1
(0H
:
Not mounted,
1H
:
CC-Link,
2H
:
DeviceNet,
3H
:
PROFIBUS-DP,
6H
:
EtherCAT,
7H
:
EtherNet/IP,
9H
:
PIO,
AH
:
PROFINET IO,
DH
:
CC-Link IE)
226 I/O1 Fieldbus Node Address
1
Optional
Settable Range
0 to 125
Summary of Contents for R-unit RSEL
Page 2: ......
Page 5: ...ME0392 4C 2 Quick Start Guide Japanese Only ...
Page 32: ...Actuator Coordinate System Intro 18 ME0392 4C 2 Slider type 3 Table type 0 0 0 0 ...
Page 50: ...Chapter 1 RSEL System 1 4 Installation 1 13 ME0392 4C ...
Page 244: ...Chapter 4 Unit connection Installation and Wiring 4 5 PIO Circuit 4 32 ME0392 4C ...
Page 316: ...Chapter 5 Operation 5 10 ELECYLINDER Operation 5 52 ME0392 4C ...
Page 438: ...Chapter 6 Field Network PIO SIO 6 5 Example of Connectivity Setting 6 120 ME0392 4C ...
Page 532: ...10 6 Servo Gain Adjustment 10 90 10 7 Parameter Configuration Advanced Use 10 93 ...
Page 638: ...Chapter 10 Parameter 10 7 Parameter Configuration Advanced Use 10 106 ME0392 4C ...
Page 838: ...Chapter 14 Warranty 14 Warranty 14 3 ME0392 4C ...
Page 843: ......
Page 844: ......