CHAPTER 4: INTERFACES
FRONT PANEL OVERVIEW
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
75
•
Slow flash. Alternating between the off state and the on state one time per second.
In the event of an alarm, the page containing the alarm will be promoted to active page. If
there are multiple pages with alarms, the page with the lowest page number is promoted.
If there are alarms on multiple pages, and alarms on some pages have already been
acknowledged (but not cleared) by the user, then the pages with active alarms move ahead
of the pages that have acknowledged alarms. The user will always have to navigate
through the pages of alarms to view them.
Display of alarm pages is prioritized according to active window (unacknowledged or
flashing alarm) and page number (for example, if two pages have an unacknowledged
alarm, the page with the lowest number will automatically be promoted as the displayed
page).
Self-test page
The self-test page displays any active self test alarms as well as the time of occurrence
and the severity of the alarm (yellow for non-critical and red for critical).
Figure 55: Self-test page example
Product information page
The product information page contains all of the constituent data describing the makeup
of the IED, including the order code and serial number of the IED, in addition to the device
identification name, the setting configuration name, the time of last change, the firmware
version, and the firmware release date.
Figure 56: Example product information page
The
Relay ID
value reflects the string entered as the
Relay Name
in the in the
Settings >
Protection > Power System > Installation
menu. The
Configuration
value reflects the
string entered as the
User Configuration Name
in the
Settings > Protection > Power