135
Buffered Reports OptFlds
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the option fields. The following bits are
supported by the D90
Plus
.
–
Bit 1: sequence-number.
–
Bit 2: report-time-stamp.
–
Bit 3: reason-for-inclusion.
–
Bit 4: data-set-name.
–
Bit 5: data-reference.
–
Bit 6: buffer-overflow.
–
Bit 7: entryID.
–
Bit 8: conf-revision.
Buffered Reports TrgOps
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the trigger options. The following bits are
supported by the D90
Plus
.
–
Bit 1: data-change.
–
Bit 4: integrity.
–
Bit 5: general interrogation.
Buffered Reports IntgPd
Range: 0, or 250 to 4294967295 in steps of 1
Default: 0
This setting specifies the integrity period for buffered reports.
NOTE
NOTE:
Please disconnect any IEC 61850 client connection to the D90
Plus
prior to making setting
changes to the buffered report configuration. Disconnecting the rear Ethernet connection
from the D90
Plus
will disconnect the IEC 61850 client connection.
IEC 61850 actual values
Actual values for IEC 61850 are available in two locations. A general IEC 61850
communications actual value is available through the
Actual Values > Communications >
Communication
menu. The IEC 61850 GOOSE input and output actual values are available
through the
Actual Values > Communications > Inputs/Outputs
menu.
Remote device status values
Select the
Actual Values > Communications > Inputs/Outputs > Remote Devices Status
menu item to open the remote device status values window.