CHAPTER 15: THEORY OF OPERATION
SINGLE-POLE TRIPPING
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
663
Table 44: Blocking scheme trip table for four-bit channels
Table 45: Unblocking scheme trip table for four-bit channels
Remote data
Local data
Bit pattern
Remote
determination of
fault type
Local determination
of fault type
Trip output
RX1
RX2
RX3
RX4
0
0
0
0
Any while the INIT
signal was not
established
---
Trip as for single-
bit channel
1
1
1
0
MULTI-P
AG
DIR BLOCK TRIP A
1
0
1
1
BG
AG
DIR BLOCK TRIP A
1
1
0
1
CG
AG
DIR BLOCK TRIP A
0
1
1
1
AG
AG, AB, ABG, CA, CAG,
3P, Unrecognized
DIR BLOCK TRIP A
1
0
1
1
BG
BG, AB, ABG, BC, BCG,
3P, Unrecognized
DIR BLOCK TRIP B
0
1
1
1
AG
BG
DIR BLOCK TRIP B
1
1
0
1
CG
BG
DIR BLOCK TRIP B
1
1
1
0
MULTI-P
BG
DIR BLOCK TRIP B
1
1
0
1
CG
CG, BC, BCG, CA, CAG,
3P, Unrecognized
DIR BLOCK TRIP C
0
1
1
1
AG
CG
DIR BLOCK TRIP C
1
0
1
1
BG
CG
DIR BLOCK TRIP C
1
1
1
0
MULTI-P
CG
DIR BLOCK TRIP C
0
1
1
1
AG
BC, BCG
DIR BLOCK TRIP
3P
1
0
1
1
BG
CA, CAG
DIR BLOCK TRIP
3P
1
1
0
1
CG
AB, ABG
DIR BLOCK TRIP
3P
1
1
1
0
MULTI-P
Unrecognized
DIR BLOCK TRIP
3P
Remote data
Local data
Bit pattern
Remote
determination of
fault type
Local
determination of
fault type
Trip output
RX
1
LO
G1
RX
2
LO
G2
RX
3
LO
G3
RX
4
LO
G4
0
0
0
0
0
0
1
1
MULTI-P
AG
DCUB TRIP A
0
0
0
0
0
0
0
1
MULTI-P
AG
DCUB TRIP A
0
0
1
1
0
0
0
0
BG
AG
DCUB TRIP A
0
0
0
1
0
0
0
0
BG
AG
DCUB TRIP A
0
0
0
0
1
1
0
0
CG
AG
DCUB TRIP A
0
0
0
0
0
1
0
0
CG
AG
DCUB TRIP A
1
1
0
0
0
0
0
0
AG
AG, AB, ABG, CA,
CAG, 3P,
unrecognized
DCUB TRIP A
0
1
0
0
0
0
0
0
AG
AG, AB, ABG, CA,
CAG, 3P,
unrecognized
DCUB TRIP A
0
0
1
1
0
0
0
0
BG
AG, AB, ABG, CA,
CAG, 3P,
unrecognized
DCUB TRIP B