CONTROL ELEMENTS
CHAPTER 7: PROTECTION
Consider the configuration below.
Figure 312: Breaker flashover application example
The source 1 (SRC1) phase currents are CTs and phase voltages are bus VTs. The source 2
(SRC2) phase voltages are line VTs. Contact input 1 is set as the breaker 52a contact
(optional).
The conditions prior to flashover detection are:
1.
∆
VA is greater than pickup.
2.
VAg, VBg, or VCg is greater than the pickup setting.
3.
IA, IB, IC = 0; no current flows through the breaker.
4.
52a status = 0 (optional).
The conditions at flashover detection are:
1.
∆
VA is less than pickup.
2.
VAg, VBg, or VCg is lower than the pickup setting.
3.
IA, IB, or IC is greater than the pickup current flowing through the breaker.
4.
52a status = 0 (optional).
Digital counters
There are eight identical digital counters in the D90
Plus
. A digital counter counts the
number of state transitions from logic 0 to logic 1. The counter is used to count operations
such as element pickup, changes of state of an external contact (for example, a breaker
auxiliary switch), or pulses from a watt-hour meter.
Select the
Settings > Protection > Control > Digital Counters
menu item to open the
digital counters configuration window.
Figure 313: Digital counters configuration settings
The following settings are available for each digital counter.