SELF-TESTS
CHAPTER 14: TESTING
Self-test error messages
The self-test error messages are displayed on the annunciator panel. Error messages can
be accessed from the self-test tab. The self-test tab becomes illuminates when there are
errors to report.
Figure 543: Typical self-test error page
There are three soft-keys associated with the self-test summary page.
•
The
Next Page
soft-key cycles through the pages of alarms and to the error messages
page. If there are more errors present than can be displayed, scroll bars will appear to
notify the user to scroll beyond the screen to view more error messages.
•
The
Down
soft-key allows user to cycle through the self-test error messages from top
to bottom. A white frame borders the selected self-test error message.
•
The
Detail
soft-key displays additional details of the selected error message. A
definition of problem, a graphical indication, and some possible solutions are
displayed. The following figures shows the details about the IRIG-B FAILURE self-test
error message.
Figure 544: IRIG-B failure message details
Self-test errors are classed as minor errors and major errors. The major self-test error
messages are indicated in red on the annunciator display and are described below.
AC SLOT F FIRMWARE MISMATCH
AC SLOT J FIRMWARE MISMATCH
Description: There a firmware mismatch between the AC card in the indicated slot and the
CPU.
Severity: Protection is not available, and relay is not operational.
If either of these messages appear, contact GE Grid Solutions.