414
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION FLEXLOGIC™
CHAPTER 7: PROTECTION
User Configured Event Name
Range: up to 20 alphanumeric characters
Default: ---
Each available protection FlexLogic™ operand can be renamed to a user-specified
value. This feature allows users to rename operands to allow for clearer identification or
to match specific applications. The new operand name will appear in protection and
automation logic, in settings that take operands as their value, and in event reports.
Protection FlexLogic™ operands
The following protection FlexLogic™ operands are available for the D90
Plus
. They are listed
alphabetically by operand syntax. The definitions listed below reflect the default operand
names. Some operands can be renamed within their settings window, including the names
of breakers, contact inputs, virtual inputs, and virtual outputs. All operands can also be
assigned user-defined names through the
Settings > Configure FlexOperands
menu item.
Autoreclose operands
AR 1-P RIP......................................................Asserted when a single-pole autoreclose is in progress.
AR 3-P/1 RIP.................................................Asserted when a three-pole autoreclose is in progress via dead
time 1.
AR 3-P/2 RIP.................................................Asserted when a three-pole autoreclose is in progress via dead
time 2.
AR 3-P/3 RIP.................................................Asserted when a three-pole autoreclose is in progress via dead
time 3.
AR 3-P/4 RIP.................................................Asserted when a three-pole autoreclose is in progress via dead
time 4.
AR BKR1 BLK................................................Asserted when reclosure of breaker 1 is blocked.
AR BKR2 BLK................................................Asserted when reclosure of breaker 2 is blocked.
AR CLOSE BKR1...........................................Asserted when a close breaker 1 signal is issued.
AR CLOSE BKR2...........................................Asserted when a close breaker 2 signal is issued.
AR DISABLED................................................Asserted when the autoreclose element is disabled.
AR ENABLED.................................................Asserted when the autoreclose element is enabled.
AR FORCE 3-P TRIP....................................Asserted when a trip is forced to a three-phase trip.
AR INCOMPLETE SEQ................................Asserted when a the incomplete sequence timer times out.
AR LO...............................................................Asserted when the autoreclose element is in the lockout state.
AR RESET........................................................Asserted when the autoreclose element has been reset
manually or by the reset timer.
AR RIP..............................................................Asserted when the autoreclose element is in the reclose-in-
progress state.
AR SHOT CNT > 0........................................Asserted when the first close breaker signal has been issued.
AR SHOT CNT = 1........................................Asserted when the shot count is equal to 1.
AR SHOT CNT = 2........................................Asserted when the shot count is equal to 2.
AR SHOT CNT = 3........................................Asserted when the shot count is equal to 3.
AR SHOT CNT = 4........................................Asserted when the shot count is equal to 4.
AR ZONE 1 EXTENT....................................Asserted when the zone 1 distance function is be set to the
extended over-reach value.
Auxiliary overvoltage operands
AUX OV1 DPO ..............................................Asserted when the auxiliary overvoltage element drops out.
AUX OV1 OP..................................................Asserted when the auxiliary overvoltage element operates.
AUX OV1 PKP................................................Asserted when the auxiliary overvoltage element picks up.