CHAPTER 6: COMMUNICATIONS
IEC 61850 COMMUNICATIONS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
123
Table 8: Per-unit base units
The GOOSE analog input FlexAnalog™ values are available for use in other
D90
Plus
functions that use FlexAnalog™ values.
IEC 61850 server configuration
Select the
Settings > Communications > IEC 61850 > Server Configuration
menu item to
open the IEC 61850 server configuration window.
Figure 100: IEC 61850 server configuration settings
The following settings are available.
IED Name
Range: up to 32 alphanumeric characters
Default: IEDName
This setting represents the MMS domain name where all IEC/MMS logical nodes are
located. Changes to this setting and the GOOSE dataset will not take effect until the unit
is restarted. The setting value can be composed of up to 32 characters, including upper
and lowercase letters, numbers, and the underscore (_) character. The first character in
the string must be a letter.
Logical Device Instance
Range: up to 32 alphanumeric characters
Default: LDInst
This setting represents the IEC 61850 logical device where all IEC/MMS logical nodes are
located. The setting value can be composed of up to 32 characters, including upper and
lowercase letters, numbers, and the underscore (_) character. The first character in the
string must be a letter.
LPHD DC PhyNam Location
Range: up to 80 ASCII characters
Default: Location
This setting represents a string that appears within the PhyName of the LPHD node. It
can be composed of up to 80 characters, including upper and lowercase letters,
numbers, and the underscore (_) character. The first character in the string must be a
letter.
Element
Base unit
Frequency
1 Hz
Phase angles
360 degrees
Power factor
1.00
Source current
Maximum nominal primary RMS value of the +IN and –IN inputs
Source power
Maximum value of the product of the voltage and current base
values for the +IN and –IN inputs.
Source voltage
Maximum nominal primary RMS value of the +IN and –IN inputs.