CHAPTER 7: PROTECTION
CONTROL ELEMENTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
369
Figure 307: Breaker configuration logic, sheet 4 of 4
Breaker flashover
The detection of breaker flashover is based on the following condition.
1.
Breaker open.
2.
Voltage drop measured from either side of the breaker during the flashover period.
3.
Voltage difference drop.
4.
Measured flashover current through the breaker.
Furthermore, the breaker flashover scheme is applicable for cases where either one or two
sets of three-phase voltages are available across the breaker.
Function
SETTING
= Disabled
= Enabled
BKR1 SUBST ON
FLEXLOGIC OPERANDS
BKR1 SUBST OPENED
AND
AND
AND
OR
AND
BKR1 DISCREPANCY
FLEXLOGIC OPERAND
0
t
Discrepancy Time
SETTING
BKR1 ANY POLE OPEN
FLEXLOGIC OPERAND
BKR1 ONE POLE OPEN
FLEXLOGIC OPERAND
BKR1 BAD STATUS
FLEXLOGIC OPERAND
BKR1 BAD INTERMED
FLEXLOGIC OPERAND
870023A3.CDR
OR
Breaker In Local
SETTING
Off = 0
BKR1 OOS
FLEXLOGIC OPERAND
BKR1 A OPENED
BKR1 B OPENED
BKR1 C OPENED
BKR1 A OPENED
AND
AND
AND
OR
BKR1 A CLOSED
BKR1 B CLOSED
BKR1 C CLOSED
BKR1 A CLOSED
BKR1 SUBST CLOSED
AND
AND
OR
BKR1 OPENED
FLEXLOGIC OPERAND
AND
AND
OR
BKR1 CLOSED
FLEXLOGIC OPERAND
1 POLE
BKR1 BAD STATUS
BKR1 A OPENED
BKR1 B CLOSED
BKR1 C CLOSED
AND
AND
BKR1 A CLOSED
BKR1 B OPENED
BKR1 C CLOSED
AND
BKR1 A CLOSED
BKR1 B CLOSED
BKR1 C OPENED
AND
AND
AND
BKR1 A BAD STATUS
BKR1 B BAD STATUS
BKR1 C BAD STATUS
OR
AND
AND
AND
OR
BKR1 A INTERMED
BKR1 B INTERMED
BKR1 C INTERMED
OR
AND
OR
AND