CHAPTER 3: INSTALLATION
ELECTRICAL INSTALLATION
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
61
Figure 30: Direct input and output dual channel connection
The interconnection requirements are described in further detail in this section for each
specific variation of inter-relay communications module. These modules are listed in the
following table. All fiber modules use ST type connectors.
Table 3: Channel communication options
DANGER
DANGER:
The 850 nm module uses a class 1 VCSEL laser which is very harmful to the eye.
Observing any fiber transmitter output may cause serious injury to the eye!
Direct input and output link LEDs
The link LEDs for channels 1 and 2 are located on the rear of the inter-relay
communications card as shown below.
Module
Specification
B
G.703, 64/128 kbps, two channels
C
RS422, 64/128 kbps, two channels, two clock inputs
D
850 nm, 64/128 kbps, ST multi-mode laser, two channels with DDMI