276
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
GROUPED PROTECTION ELEMENTS
CHAPTER 7: PROTECTION
Figure 238: Breaker failure configuration settings
The following settings are available for each breaker failure element.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the breaker failure protection element.
Mode
Range: 1-Pole, 3-Pole
Default: 1-Pole
This setting selects the breaker failure operating mode: single-pole or three-pole.
Source
Range: LINE (SRC 1), BKR 1 (SRC 2), BKR 2 (SRC 3)
Default: LINE (SRC 1)
This setting selects the signal source for the breaker failure protection element.
Current Supervision
Range: Yes, No
Default: Yes
If set to “Yes”, the breaker failure element will only be initiated if current flowing through
the breaker is above the supervision pickup level.