LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
UPGRADE SOFTWARE
CHAPTER 16: MAINTENANCE
To save a settings file in the URS format in EnerVista Offline Window:
1.
In EnerVista, right-click in the Offline Window area and select
New Settings File.
A
window opens.
2.
Change the file name at the end of the
Path
field, keeping the .urs extension.
3.
From the
Associate File with Device
drop-down list, select the D90
Plus
device. Other
fields complete automatically. Otherwise, when you do not select a device from the
drop-down list, all fields need to be completed manually and only devices that match
the entered order code and version display in the list.
4.
The
Serial # Lock
field is the serial number of the intended device. It ensures that the
settings file is sent only to the specific relay that matches the serial number.
5.
Click the
OK
button to create the .urs file in the Offline Window area.
Restore settings
D90
Plus
device settings can be restored to the values they were at when a URS backup file
was created using the EnerVista UR
Plus
Setup software. Note that TFTP cannot be used
here, as TFTP "put" mode is disabled for security reasons.
To restore completely, a few settings need to be entered manually using EnerVista UR
Plus
Setup software. If the restore operation is to be via Ethernet, first the D90
Plus
device must
have its IP address settings entered under
Settings > Communications > Network >
Ethernet
.
When importing a file, it cannot have a blank numeric value. All numeric values must be
non-blank, otherwise the file is rejected.
To restore settings from a URS file:
1.
In EnerVista, connect to the device in the Online Window area.
2.
Right-click the .urs file in the Offline Window area and select
Add Existing Settings
File
to locate a file, and/or drag-and-drop the file from the Offline Window area to the
device in the Online Window area.
3.
Manually enter the following settings not transferred to the D90
Plus
with the setting
files.
Modbus Slave Address
Modbus TCP Port Number
Serial Port
Baud Rate
Parity
Minimum Response Time
Connection
IP Subnet Mask
IP Routing
Upgrade software
In general, the latest releases of the EnerVista software can be used with all firmware
versions, for example EnerVista software released for D90
Plus
1.7 can be used to access
multiple D90
Plus
devices that have version 1.7x and 1.8x firmware installed.
The latest EnerVista software and firmware can be downloaded from
https://www.gegridsolutions.com/multilin