140
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
REAL TIME CLOCK
CHAPTER 6: COMMUNICATIONS
Figure 115: FlexStates actual values
The following actual values are available for each FlexState parameter.
Name
Range: any FlexLogic™ operand
This actual value indicates the FlexLogic™ operand assigned to the FlexState parameter.
Value
Range: OFF, ON
This actual value indicates the logic state (ON, OFF) of the FlexState parameter.
Real time clock
The date and time can be synchronized a known time base and to other devices using an
IRIG-B signal. It has the same accuracy as an electronic watch, approximately ±1 minute
per month. If an IEEE 1344 compliant IRIG-B generator is connected to the D90
Plus
, then no
additional information is required. Otherwise, only the current year needs to be entered.
Use the Set Date and Time command to manually set the relay clock.
The daylight savings time (DST) settings can be used to allow the D90
Plus
clock can follow
the DST rules of the local time zone. Note that when IRIG-B time synchronization is active,
the DST settings are ignored. The DST settings are used when the D90
Plus
is synchronized
with SNTP, or when neither SNTP nor IRIG-B is used.
Select the
Settings > Communications > Real Time Clock
menu item to open the real time
clock configuration window.