LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION INPUTS AND OUTPUTS
CHAPTER 7: PROTECTION
Figure 323: Protection virtual output settings
The following settings are available for each protection virtual output. If not assigned, the
virtual output will be forced to off (logic 0).
ID
Range: up to 12 alphanumeric characters
Default: Virt Op 1
This setting specifies an identifier that may be assigned to each protection virtual
output.
Events
Range: Enabled, Disabled
Default: Disabled
If this setting is “Enabled”, every change in the protection virtual output state will trigger
an event in the sequence of events recorder.
Protection virtual output actual values
Select the
Actual Values > Protection > Protection Inputs/Outputs > Virtual Outputs
menu item to open the protection virtual outputs actual values window.
Figure 324: Protection virtual output actual values
The following actual values are available for all configured protection virtual outputs.