CHAPTER 7: PROTECTION
GROUPED PROTECTION ELEMENTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
263
Figure 223: Inverse time undervoltage curves
NOTE
NOTE:
At 0% of pickup, the operating time is equivalent to the undervoltage delay setting.
Phase undervoltage
The phase undervoltage element may be used to give a desired time delay operating
characteristic versus the applied fundamental voltage (phase-to-ground or phase-to-
phase for wye VT connections, or phase-to-phase for delta VT connections) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the
dropout voltage.
Select the
Settings > Protection > Elements > Group 1 > Voltage > Phase UV
menu item
to open the phase undervoltage configuration window.
Figure 224: Phase undervoltage configuration settings
The following settings are available for each phase undervoltage element.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the phase undervoltage protection element.
Signal Source
Range: LINE (SRC 1), BKR 1 (SRC 2), BKR 2 (SRC 3)
Default: LINE (SRC 1)
This setting selects the signal source for the phase undervoltage protection element.