AUTOMATION INPUTS AND OUTPUTS
CHAPTER 8: AUTOMATION
Table 32: Nominal voltage setting for typical battery voltages
Events
Range: Enabled, Disabled
Default: Enabled
If this setting is “Enabled”, every change in the contact input state will trigger an event in
the sequence of events recorder.
Contact input chatter detection
The D90
Plus
has a chatter detection feature. When enabled, the IED monitors the number
of state changes that occur within a set duration. If this value exceeds a set value, then a
trouble condition is declared for the input and the
CONTACT INPUT TROUBLE
operand is
asserted.
The input trouble alarm impacts relay functionality as follows:
•
Automation logic operands: operand state will be blocked.
•
DNP 3.0 communications: reporting of the input is blocked.
•
IEC 60870-5-104 communications: reporting of the input is blocked.
•
IEC 61850 GSSE and IEC 61850 GOOSE: reporting of the input is blocked.
•
Sequence of events recorder: reporting of the input is blocked.
The trouble condition resets if the input undergoes no state changes for a duration equal
to twice the chatter time setting.
Figure 394: Chatter detection example
Select the
Settings > Automation > Automation Inputs/Outputs > Contact Inputs >
Chatter Detection
menu item to access the contact input chatter detection settings.
Figure 395: Contact input chatter detection configuration
Nominal voltage
Validation threshold
24 V
20 V
48 V
33.6 V
125 V
87.5 V
250 V
175 V