LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION FLEXLOGIC™
CHAPTER 7: PROTECTION
NEG SEQ DIR OC2 REV.............................Asserted when the negative-sequence directional overcurrent
2 element reverse mode operates.
Negative-sequence instantaneous overcurrent operands
NEG SEQ IOC1 DPO...................................Asserted when the negative-sequence instantaneous
overcurrent 1 element drops out.
NEG SEQ IOC1 OP ......................................Asserted when the negative-sequence instantaneous
overcurrent 1 element operates.
NEG SEQ IOC1 PKP....................................Asserted when the negative-sequence instantaneous
overcurrent 1 element picks up.
NEG SEQ IOC2
..............................................The operands listed above are also available for negative-
sequence instantaneous overcurrent 2.
Negative-sequence overvoltage operands
NEG SEQ OV DPO.......................................Asserted when the negative-sequence overvoltage element
drops out.
NEG SEQ OV OP ..........................................Asserted when the negative-sequence overvoltage element
operates.
NEG SEQ OV PKP........................................Asserted when the negative-sequence overvoltage element
has picks up.
Negative-sequence time overcurrent operands
NEG SEQ TOC1 DPO..................................Asserted when the negative-sequence time overcurrent 1
element drops out.
NEG SEQ TOC1 OP.....................................Asserted when the negative-sequence time overcurrent 1
element operates.
NEG SEQ TOC1 PKP...................................Asserted when the negative-sequence time overcurrent 1
element picks up.
NEG SEQ TOC2
.............................................The operands listed above are also available for negative-
sequence time overcurrent 2.
Neutral instantaneous overcurrent operands
NEUTRAL IOC1 DPO..................................Asserted when the neutral instantaneous overcurrent 1
element drops out.
NEUTRAL IOC1 OP .....................................Asserted when the neutral instantaneous overcurrent 1
element operates.
NEUTRAL IOC1 PKP ...................................Asserted when the neutral instantaneous overcurrent 1
element picks up.
NEUTRAL IOC2 to 12
.................................The operands listed above are also available for neutral
instantaneous overcurrent 2 through 12.
Neutral overvoltage operands
NEUTRAL OV1 DPO....................................Asserted when the neutral overvoltage 1 element drops out.
NEUTRAL OV1 OP.......................................Asserted when the neutral overvoltage 1 element operates.
NEUTRAL OV1 PKP.....................................Asserted when the neutral overvoltage 1 element picks up.
NEUTRAL OV2 to 3
.....................................The operands listed above are also available for neutral
overvoltage 2 and 3.
Neutral time overcurrent operands
NEUTRAL TOC1 DPO.................................Asserted when the neutral time overcurrent 1 element drops
out.
NEUTRAL TOC1 OP ....................................Asserted when the neutral time overcurrent 1 element
operates.
NEUTRAL TOC1 PKP..................................Asserted when the neutral time overcurrent 1 element picks up.