Locking FlexLogic™ equations to a serial number
A settings file and associated FlexLogic™ equations can also be locked to a specific
D90
Plus
serial number. Once the desired FlexLogic™ entries in a settings file have been
secured, use the following procedure to lock the settings file to a specific serial number.
1.
Select the settings file in the offline window.
2.
Right-click on the file and select the
Manage Settings File > Edit Properties
item.
The following window is displayed.
3.
Enter the serial number of the D90
Plus
device to lock to the settings file in the
Serial #
Lock
field.
The settings file and corresponding secure FlexLogic™ equations are now locked to the
D90
Plus
device specified by the serial number.
Settings file traceability
A traceability feature for settings files allows the user to quickly determine if the settings in
a D90
Plus
device have been changed since the time of installation from a settings file.
When a settings file is transferred to a D90
Plus
device, the date, time, and serial number of
the D90
Plus
are sent back to EnerVista UR
Plus
Setup and added to the settings file on the
local PC. This information can be compared with the D90
Plus
actual values at any later date
to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is
either transferred to the D90
Plus
device or obtained from the D90
Plus
device. Any partial
settings transfers by way of drag and drop do not add the traceability information to the
settings file.