600
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
METERING SUMMARY EDITOR
CHAPTER 12: LOCAL INTERFACE
Figure 534: Metering configuration window
Text
Range: up to 20 alphanumeric characters
Default: ---
This setting defines the selected metering cell as a text box. These are typically used as
headings. Specify up to 10 alphanumeric characters.
Parameter
Range: any FlexAnalog™ parameter
Default: Digital Counter 1 Value
This setting selects a FlexAnalog™ parameter that specifies the metered value to display
in the metering cell.
Units
Range: up to 4 alphanumeric characters
Default: ---
This setting specifies a four-character alphanumeric string that is used in the metering
cell display for the corresponding metered value.
Scale Factor
Range: G (Giga), M (Mega), k (kilo), None
Default: None
This setting allows the user to select a scaling factor for displayed metered value. The
range is restricted to correspond to the selected analog value parameter.
Multiplier
Range: dependent on selected analog value
Default: ---
This setting allows the user to specify a multiplier for the metering parameter value if the
scaling factor is set to “None”. The range is restricted to correspond to the selected
actual value parameter.