494
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
BREAKER MANAGEMENT
CHAPTER 9: EQUIPMENT MANAGER
Figure 425: Equipment manager block diagram
Breaker management
This section describes the breaker management features of the equipment manager.
Circuit breaker arcing
The breaker arcing function provides indications of the condition of the circuit breaker
interrupter. The primary function is measurement of accumulated contact wear. This is
accomplished by integrating the current passing through the breaker during interruption.
The function compares the accumulated arcing current with manufacturer data to provide
an indication that the breaker requires maintenance. The function also measures the total
clearing time, and the maximum interrupted current. This latter value is compared with
manufacturer data to determine if the interrupt rating of the breaker has been exceeded.