FlexPDU User Manual

1

FlexPDU User Manual

Summary of Contents for FlexPDU

Page 1: ...FlexPDU User Manual 1 FlexPDU User Manual ...

Page 2: ...ns 3 Ⅴ Product sketch 4 Ⅶ Mounting method 4 Ⅷ Hardware introduction 5 1 Front panel introduction 5 2 Initialization 5 3 Hardware settings 7 4 Daisy chain connection 8 Ⅸ Software introduction 9 1 Web browser access 9 2 SNMP access 15 3 Telnet access 21 Ⅹ Technical Specification 22 Ⅺ Quality Warranty 24 ...

Page 3: ...gement and hot swappable technology Ⅱ Main functions 1 Monitor input voltage 2 Monitor total load current 3 Monitor total power kW 4 Monitor energy consumption kWh 5 Monitor the micro environment in the cabinet Ⅲ Monitoring method Via software FlexPDUs can be monitored and managed though centralized management software CLEVER Manager Ⅳ Applications Apply to single phase 100VAC 240VAC up to 63Amps ...

Page 4: ...e GND 3 Green White RS485 A 4 Blue RS485 A 5 Blue White RS485 B 6 Green RS485 B Brown White GND 8 Brown GND 1 Screen TFT screen 2 RUN Run indicator KWH kWh indicator ALM Alarm indicator 3 NET Ethernet port 4 SER Daisy chain port 5 LINK Daisy chain port 6 MENU Menu Key 7 UP Function set key 8 DOWN Position selection key 9 RESET Restart button 10 T H Temperature Humidity sensor port 2 3 1 6 7 8 9 4 ...

Page 5: ...t the Master or Slave address cord the maximum threshold of voltage current temperature and humidity from 0 to 9 DOWN Position selection key light up the LCM background to select the address cord maximum threshold of voltage current temperature and humidity RESET Restart button Restart the device Screen View the states display the power and environment date T H Temperature and humidity sensor port...

Page 6: ...1A Volts 220VAC Power 0 0kW kWh 0 0kWh Figure 1 2nd screen L2 Amps 0 1A Volts 220VAC Power 0 0kW kWh 0 0kWh Figure 2 3rd screen L3 Amps 0 1A Volts 220VAC Power 0 0kW kWh 0 0kWh Figure 3 4th screen the temperature and humidity date figure 4 5th screen the brad rate 4800 9600 19200 38400 Figure 5 Figure 1 Figure 2 Figure 3 Press MENU Press MENU TTON 键切换 Figure 1 Figure 2 Figure 3 216VDC 00 0A 00 0KW...

Page 7: ...hreshold setting page like L1 32 0A 276VAC Press DOWN key to select the value need to be set the select position will flesh then press UP key to set the threshold value the allowed maximum current is 32A and maximum voltage is 276VAC Note All above settings must be saved by pressing the MENU key and the settings will take effective after the beep sound otherwise the device will without saving the ...

Page 8: ...ed will be displayed in the screen 4 Daisy chain connection Serial Daisy chain mode Figure 1 4 1 Setting one FlexPDU as Master unit and the rest as Slave unit The maximum daisy chain is 4pcs Apply to FlexPDU refer to figure 1 Ethernet Daisy chain mode Figure 2 4 2 Connect the each FlexPDU to the port from the HUB and connect the Net port from HUB to the internet No limitation for the FlexPDU quant...

Page 9: ...can access monitor and control the FlexPDU by web browser like Internet Explorer google chrome and etc by input the correct IP address in the address bar The pop up login window is illustrated as figure 1 Figure1 User will see the home page as figure 2 after entering the correct user name and password eaton eaton in the login dialog box Figure 2 Company Logo MENU ...

Page 10: ...op down list From the drop down list view the power date or Master unit or Slave units One Master unit can support to you 4 Slave unit Slave 1 Slave 4 B Threshold setting to set threshold of total load current See below User can set up the threshold of current voltage temperature and humidity from the threshold settings page as figure 3 Figure 3 Set up the threshold of current voltage temperature ...

Page 11: ...r Mute Set ON enable alarm mute function and alarm beeping sound is shut down Set OFF turn off alarm mute alarm beeping sound is opened Work mode Revise master and slave mode to set slave1 2 Virtual Value 1 4 b Energy Setting Clear energy line1 Click button The same operation for Line 2 and Line3 in 3phase products Figure 4 D User settings as figure 5 ...

Page 12: ...FlexPDU User Manual 12 Figure 5 User can revise the user name and password the save it the Max length of user name and password is 10digits E Networking Setting as figure 6 Figure 6 1 Networking Setting ...

Page 13: ...modification of the network settings 2 Telnet settings Select from ON or OFF to configure the Telnet feature the default state is ON F SNMP Setting see below figure 7 Figure 7 1 SNMP V1 V2c settings The default get community and Set community is public and private User can modify according to the specific application Fill in the trap address of SNMP management platform trap alarm will be sent auto...

Page 14: ...sword SMTP server and port send to account then save Click Testing and fill in the testing email address If the test email is received the setting is effective See below interface Figure 8 H Restart as figure 9 Select Activity user can restart the software or restore to factory default settings After click Save when FlexPDU buzzing the software restart is successful See below Note Press and hold t...

Page 15: ...ter device name deviceDescription 1 3 6 1 4 1 534 6 6 8 1 2 Device Description deviceVersion 1 3 6 1 4 1 534 6 6 8 1 3 Device version ipAddr 1 3 6 1 4 1 534 6 6 8 1 4 Device IP Address macAddr 1 3 6 1 4 1 534 6 6 8 1 5 Master device mac Address s1macAddress 1 3 6 1 4 1 534 6 6 8 1 6 Slave1 device mac Address s2macAddress 1 3 6 1 4 1 534 6 6 8 1 7 Slave2 device mac Address s3macAddress 1 3 6 1 4 1 ...

Page 16: ...4 6 6 8 2 20 Slave4 Line3 Voltage mCurrentA 1 3 6 1 4 1 534 6 6 8 3 1 Master Line1 Current Magnified 10 times s1CurrentA 1 3 6 1 4 1 534 6 6 8 3 2 Slave1 Line1 Current Magnified 10 times s2CurrentA 1 3 6 1 4 1 534 6 6 8 3 3 Slave2 Line1 Current Magnified 10 times s3CurrentA 1 3 6 1 4 1 534 6 6 8 3 4 Slave3 Line1 Current Magnified 10 times s4Current A 1 3 6 1 4 1 534 6 6 8 3 5 Slave4 Line1 Current ...

Page 17: ...ave 4 Line3 Active Power mAppPowerA 1 3 6 1 4 1 534 6 6 8 5 1 Master Line1 Apparent Power s1AppPowerA 1 3 6 1 4 1 534 6 6 8 5 2 Slave1 Line1 Apparent Power s2AppPowerA 1 3 6 1 4 1 534 6 6 8 5 3 Slave2 Line1 Apparent Power s3AppPowerA 1 3 6 1 4 1 534 6 6 8 5 4 Slave3 Line1 Apparent Power s4AppPowerA 1 3 6 1 4 1 534 6 6 8 5 5 Slave4 Line1 Apparent Power mAppPowerB 1 3 6 1 4 1 534 6 6 8 5 6 Master Li...

Page 18: ...gy Magnified 10 times mSensorStatus 1 3 6 1 4 1 534 6 6 8 7 1 Master Sensor Status 0 unconnected 1 connection s1SensorStatus 1 3 6 1 4 1 534 6 6 8 7 2 Slave1 Sensor Status 0 unconnected 1 connection s2SensorStatus 1 3 6 1 4 1 534 6 6 8 7 3 Slave2 Sensor Status 0 unconnected 1 connection s3SensorStatus 1 3 6 1 4 1 534 6 6 8 7 4 Slave 3 Sensor Status 0 unconnected 1 connection s4SensorStatus 1 3 6 1...

Page 19: ...oltage Alarm 1 normal 2 low 3 high s4VolAlarmB 1 3 6 1 4 1 534 6 6 8 8 10 Slave4 Line2 Voltage Alarm 1 normal 2 low 3 high mVolAlarmC 1 3 6 1 4 1 534 6 6 8 8 11 Master Line3Voltage Alarm 1 normal 2 low 3 high s1VolAlarmC 1 3 6 1 4 1 534 6 6 8 8 12 Slave1 Line3 Voltage Alarm 1 normal 2 low 3 high s2VolAlarmC 1 3 6 1 4 1 534 6 6 8 8 13 Slave2 Line3 Voltage Alarm 1 normal 2 low 3 high s3VolAlarmC 1 3...

Page 20: ...Alarm 1 normal 2 low 3 high mCurAlarmC 1 3 6 1 4 1 534 6 6 8 9 11 Master Line3 Current Alarm 1 normal 2 low 3 high s1CurAlarmC 1 3 6 1 4 1 534 6 6 8 9 12 Slave1 Line3 Current Alarm 1 normal 2 low 3 high s2CurAlarmC 1 3 6 1 4 1 534 6 6 8 9 13 Slave2 Line3 Current Alarm 1 normal 2 low 3 high s3CurAlarmC 1 3 6 1 4 1 534 6 6 8 9 14 Slave3 Line3 Current Alarm 1 normal 2 low 3 high s4CurAlarmC 1 3 6 1 4...

Page 21: ...ve Power s4TotalActPower 1 3 6 1 4 1 534 6 6 8 11 5 Slave 4 Total Active Power mTotalAppPower 1 3 6 1 4 1 534 6 6 8 11 6 Master Total Apparent Power s1TotalAppPower 1 3 6 1 4 1 534 6 6 8 11 7 Slave 1 Total Apparent Power s2TotalAppPower 1 3 6 1 4 1 534 6 6 8 11 8 Slave 2 Total Apparent Power s3TotalAppPower 1 3 6 1 4 1 534 6 6 8 11 9 Slave 3 Total Apparent Power s4TotalAppPower 1 3 6 1 4 1 534 6 6...

Page 22: ...rameters 1 Input Single phase Rating voltage 110 220V 50 60HZ The max current 16A 32A 63A Three phase Rating voltage 380V 50 60HZ The max current 3 16A 3 32A Direct current Rating voltage 240V 336V The max current 40A 60A Cable Spec 16A 3 2 5mm2 3M 32A 3 6 0mm2 3M 63A 3 16 0mm2 3M 3 16A 5 2 5mm2 3M 3 32A 5 6 0mm2 3M Input terminal 16A input 3 2 5mm2 3M IEC60320 C20 input 32A input 3 6 0mm2 3M IEC6...

Page 23: ...ay direction Vertical kWh Accuracy 1 Resolution 0 1kWh Respond time 400ms Display method LCD Display direction Vertical 5 Physical Spec Material ABS PC Color Black Dimension Build in FlexPDU modular 155mm Hot Swap FlexPDU modular 180mm 6 Installation Vertical 7 Monitor Total load current Input Voltage Total energy consumption kWh Total Power kW Temperature humidity 8 Setting Threshold of Amps Volt...

Page 24: ...company for repair If the product has been beyond the warrant for repairing time or it has been damaged by accident negligence or misapplication you should pay some repair charge The above warranty does not apply to the following situation 1 The damage caused by customers incorrect or inadequate repair 2 The damage caused by unauthorized modification or misusing 3 The damage caused by using out of...