FlexPDU User Manual
7
6th screen: the device IP, address code(from 0 to 4) (Figure 6)
7th screen: L1 threshold of the current (32A)and voltage(276VAC) (Figure 7)
8th screen: L2 threshold of the current (32A)and voltage(276VAC) (Figure 8)
9th screen: L3 threshold of the current (32A)and voltage(276VAC) (Figure 9)
10th screen: the threshold of the temperature(40
℃
) and humidity(90%) (Figure 10)
3. Hardware settings
3.1 Address code settings: To locate the address code page(like Add -0) from the LCD screen, press DOWN
key to set the value which cycling from 4 to 0 for the master or slave address code and
press UP key to set the value which cycling from 0 to 4, the address code range from 0
to 4.
3.2. Current or Voltage threshold settings: To locate the threshold setting page(like L1 32.0A 276VAC);
Press DOWN key to select the value need to be set, the select position will flesh, then
press UP key to set the threshold value, the allowed maximum current is 32A and
maximum voltage is 276VAC
Note: All above settings must be saved by pressing the MENU key, and the settings will take effective after
the beep sound, otherwise, the device will without saving the settings.
3.3 Restore to factory settings: Press and hold the MENU key when power on or Hold the MENU key to
(
Figure 1
)
(
Figure 2
)
(
Figure 3
)
Press MENU
Press MENU
示
(
Figure 5
)
(
Figure 4
)
Press
MENU
L3 216
VAC
00.0
A
00.0
KW
000000.0KWh
L2 216
VAC
00.0
A
00.0
KW
000000.0KWh
L1 216
VAC
00.0
A
00.0
KW
000000.0KWh
Temp
00
℃
Hum
00
%
IP
192.168.
1.165
Addr 0
L1
Max
276V
32.0A
Press MENU
Press MENU
显示
Press MENU
至下一屏显示
(
Figure 7
)
(
Figure 6
)
L2
Max
276V
32.0A
Press MENU
(
Figure 8
)
Press
MENU
L3
Max
276V
32.0A
Baud
9600
Press MENU
Max
40
℃
99
%
(
Figure 9
)
(
Figure 10
)