FlexPDU User Manual
22
line are as following: STATUS
、
REBOOT
、
RESET
、
HELP
A
、
STATUS
“STATUS”command line can be used to view the device states like amps/volts/kWh or
temperature/humidity:
Command form: STATUS
【
INDEX
】
【
INDEX
】
: 0 is master, 1-4 is slave
For example:status 0:To view the amps/volts/kWh and temperature/humidity of the Master unit
Note: the actual value should be 10time of displayed one
B
、
REBOOT
Entry REBOOT command line to restart the device.
C
、
RESET
Entry RESET command line to restore to factory settings.
Ⅹ
.Technical Specification
No.
Item
Parameters
1
Input
Single
phase
Rating voltage
110/220V
50/60HZ
The max current
16A
、
32A
、
63A
Three
phase
Rating voltage
380V
50/60HZ
The max current
3×16A
、
3×32A
Direct
current
Rating voltage 240V /336V
The max current 40A / 60A
Cable Spec
16A:3×2.5mm
2
×3M
32A:3×6.0mm
2
×3M
63A:3×16.0mm
2
×3M
3×16A:5×2.5mm
2
×3M
3×32A:5×6.0mm
2
×3M
Input terminal
16A input:3×2.5mm
2
×3M IEC60320 C20 input
32A input:3×6.0mm
2
×3M IEC60309 industrial plug
63A input:3×16.0mm
2
×3M IEC60309 industrial plug
3×16A input:5×2.5 mm
2
×3M IEC60309 industrial plug
3×32A input:5×6 mm
2
×3M IEC60309 industrial plug
Overload protector
Circuit breaker
(
optional
)
2
Output
Single
phase
Rating voltage 110/220V
The max
current
16A
、
32A
、
63A
Three
phase
Rating voltage
220V
The max
current
3×16A
、
3×32A