![Eaton FlexPDU User Manual Download Page 23](http://html.mh-extra.com/html/eaton/flexpdu/flexpdu_user-manual_526534023.webp)
FlexPDU User Manual
23
Direct
current
Rating voltage 240V /336V
The max current 40A / 60A
Outlet standard
Optional
Outlet quantity
Optional
3
Display
Display method
LCD display
Display contents
Amps/volts/kWh/kW, IP address, address code, the
temperature/humidity
Accur
acy
Voltage
Accuracy:±(1
﹪
+3byte)
Resolution:1V
Respond time:400ms
Display method:LCD;
Display
direction:Vertical
Current
Accuracy:±(1
﹪
+1byte)
Resolution:100mA
Respond
time:400ms
Display
method:LCD;
Display
direction:Vertical
kWh
Accuracy:±1
﹪
Resolution:0.1kWh
Respond
time:400ms
Display method:LCD;
Display direction:Vertical
5
Physical Spec
Material
ABS+PC
Color
Black
Dimension
Build-in FlexPDU modular 155mm
Hot-Swap FlexPDU
modular
180mm
6
Installation
Vertical
7
Monitor
Total load current
Input Voltage
Total energy consumption
(
kWh
)
Total Power (kW)
Temperature/humidity
8
Setting
Threshold of Amps/Volts/Temperature and humidity
Email alarm address
HTTP
SNMP
(
V1V2c/V3c
)
Network
(
IP, gateway, subnet mask, DNS
)
9
Alarm
System
default
alarm
When current exceed Max
When voltage exceed Max
User
defined
When current exceed the threshold
When voltage exceed the threshold