FlexPDU User Manual
21
s4TemAlarm
1.3.6.1.4.1.534.6.6.8.10.5
Slave4 Temperature Alarm.
(1: normal
2: low
3: high)
mHumAlarm
1.3.6.1.4.1.534.6.6.8.10.6
Master Humidity Alarm.
(1: normal
2: low
3: high)
s1HumAlarm
1.3.6.1.4.1.534.6.6.8.10.7
Slave1 Humidity Alarm.
(1: normal
2: low
3: high)
s2HumAlarm
1.3.6.1.4.1.534.6.6.8.10.8
Slave2 Humidity Alarm.
(1: normal
2: low
3: high)
s3HumAlarm
1.3.6.1.4.1.534.6.6.8.10.9
Slave3 Humidity Alarm.
(1: normal
2: low
3: high)
s4HumAlarm
1.3.6.1.4.1.534.6.6.8.10.10
Slave4 Humidity Alarm.
(1: normal
2: low
3: high)
mTotalActPower
1.3.6.1.4.1.534.6.6.8.11.1
Master Total Active Power.
s1TotalActPower
1.3.6.1.4.1.534.6.6.8.11.2
Slave 1 Total Active Power.
s2TotalActPower
1.3.6.1.4.1.534.6.6.8.11.3
Slave 2 Total Active Power.
s3TotalActPower
1.3.6.1.4.1.534.6.6.8.11.4
Slave 3 Total Active Power.
s4TotalActPower
1.3.6.1.4.1.534.6.6.8.11.5
Slave 4 Total Active Power.
mTotalAppPower
1.3.6.1.4.1.534.6.6.8.11.6
Master Total Apparent Power.
s1TotalAppPower
1.3.6.1.4.1.534.6.6.8.11.7
Slave 1 Total Apparent Power.
s2TotalAppPower
1.3.6.1.4.1.534.6.6.8.11.8
Slave 2 Total Apparent Power.
s3TotalAppPower
1.3.6.1.4.1.534.6.6.8.11.9
Slave 3 Total Apparent Power.
s4TotalAppPower
1.3.6.1.4.1.534.6.6.8.11.10
Slave 4 Total Apparent Power.
mPhase
1.3.6.1.4.1.534.6.6.8.12.1
Master Phase.
s1Phase
1.3.6.1.4.1.534.6.6.8.12.2
Slave 1 Phase.
s2Phase
1.3.6.1.4.1.534.6.6.8.12.3
Slave 2 Phase.
s3Phase
1.3.6.1.4.1.534.6.6.8.12.4
Slave 3 Phase.
s4Phase
1.3.6.1.4.1.534.6.6.8.12.5
Slave 4 Phase.
3. Telnet access
The application of Telnet enable the user to remotely manager the FlexPDU easily. The user can
monitor and manage the device by entry the command line from the Telnet program. Telnet require the
the customer terminal from the PC and there are free software like PUTTY available. The main command