CHAPTER 6: COMMUNICATIONS
IEC 61850 COMMUNICATIONS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
121
Operand
Range: any automation logic or FlexLogic™ operand
Default: Off
This setting specifies the FlexLogic™ operand assigned to DNA point 1.
Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of remote output DNA bit pair events in the
sequence of events recorder.
Remote outputs: UserSt bit pairs
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote
devices. Each digital point in the message must be programmed to carry the state of a
specific FlexLogic™ operand. The setting above is used to select the operand which
represents a specific UserSt function (as selected by the user) to be transmitted.
Select the
Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Inputs/Outputs > Remote Outputs UserSt
menu item to open the remote inputs
configuration window.
Figure 98: Remote output UserSt bit pair configuration settings
The following settings are available for each of the 32 bit pairs.
Operand
Range: any FlexLogic™ operand
Default: Off
This setting specifies the FlexLogic™ operand assigned to UserSt point 1.
Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of remote output UserSt bit pair events in
the sequence of events recorder.