![Tripp Lite PDUMVR30HVNET Brochure & Specs Download Page 1](http://html1.mh-extra.com/html/tripp-lite/pdumvr30hvnet/pdumvr30hvnet_brochure-and-specs_1166262001.webp)
Single-Phase Switched PDU with outlet level
metering, 5/5.8kW 30A 208/240V, 0U Vertical
Rackmount, C19 & C13 outlets, L6-30P input
MODEL NUMBER:
PDUMVR30HVNET
Description
Tripp Lite single phase Switched PDU / Power Distribution Unit with individual outlet metering offers advanced
network control and monitoring with the ability to turn on, turn off, recycle or lock-out power to each individual
receptacle, monitor site electrical conditions and remotely monitor output power consumption for each individual
outlet. Built-in current monitoring offers 1% billing grade accuracy. PowerAlert interface supports remote control
and custom notification of user-specified conditions via email, secure web, SNMP, Telnet or SSH interface.
Individually switched outlets can be controlled in real-time to remotely reboot unresponsive network hardware, or
be custom programmed for user-defined power-up and power-down sequences to ensure proper startup of
interdependent IT systems and prevent inrush-related overloads as network equipment is first energized.
Unused PDU outlets can be electronically locked off to prevent the connection of unauthorized hardware. PDU
output current consumption in amps is continuously displayed locally via visual meter and remotely via web/network interface to warn of potential overloads
before critical IT mains or branch breakers trip.
Features
208/240V 30A Switched PDU with built-in web/network interface in 0U 70in / 178cm vertical rackmount form factor; 30A max capacity (agency derated to
24A)
Attached NEMA L6-30P 208/240V single phase input with 10 ft. / 3m cord
24 switched outlets (4 C19 / 20 C13)
Supports power-on, power-off or reboot of each outlet on a real-time or programmable basis
Enables reboot of locked equipment, custom power-on/power-off sequences, load-shedding and disabling unused outlets
Network interface provides PDU control and data regarding input voltage and load level for each load bank or each individual outlet in amps
Current monitoring provides 1% billing grade accuracy
Digital display continuously report output load level in amps
Display also supports IP-address self-identification and 180 degree display rotation
Supports user-specified alarm notification thresholds
Highlights
Switched 30A 208/240V PDU, 0U
70 in. / 178cm Vertical
Rackmount Format
Reports voltage, frequency &
load per-outlet or load bank via
ethernet interface
Visual current meter, Toolless
button mount installation
NEMA L6-30P input, attached 10
ft. / 3m cord
24 switched outlets (4 C19 / 20
C13) with cord retention brackets
Temperature, humidity and
contact closure monitoring options
Applications
Ideal for network configurations
requiring a switched, metered
and monitored PDU supporting
individual outlet rebooting, load
shedding and remote
web/network current monitoring
of critical networking components
Package Includes
Rackmount PDU
Rackmount brackets
PDUMVROTATEBRKT
1 / 4