background image

CEP 6507GU/G, 6508GU/G 

Temporary branch power distribution unit 

 with Ground Fault Protection for personnel

 

 

 

Installation and Operating Instructions 

 
SPECIFICATION 
These installation and operation instructions 
apply to the following temporary power 
branch distribution system components. Do 
not discard these instructions, save for future 
reference. 

PORATBLE POWER  

DISTRIBUTION UNITS 

These units are rated either 30 or 50 amps, 
125/250 VAC, Single Phase. The max. ampacity 
for the 30 amp unit is 60A @ 120V, and the 50 
amp unit is 80A @ 120V.  The 20 amp, 120 volt 
outlets are individually protected by circuit 
breakers and GFCI circuit modules. 
 

Model 

Number(s) 

20 Amp 

Receptacle 

6507GU, 6508GU 

U-Ground 

6507G, 6508G 

Twist Lock 

   
          
INTRODUCTION 
CEP temporary power distribution units are 
equipped with GFCI modules to provide 
protection from electrocution hazards resulting 
from ground faults.  Ground faults are current 
leaks and can result in electric shock. Currents 
of only 60/1000 of an ampere can be fatal. The 
GFCI protection provided by CEP temporary 
power distribution units significantly minimizes 
shock hazards. CEP temporary power 
distribution units,  
 

 

 
 
 

 

which are UL listed as Class A, Group I 
interrupters, respond to fault currents as low as 
3-6 milliamperes, and will shut off the current 
within 1/40

th

 of a second. The temporary power 

distribution unit is designed to provide protection 
against electrical shock hazards due to line-to-
ground faults. Although the GFCI module does 
not eliminate the hazard of a shock, it does limit 
the duration of the shock to a period considered 
safe for normally healthy persons. 
GFCI modules will provide protection against 
ground faults only. They will not protect against 
overloads or short circuits. There is no known 
device that will guard against the electrical shock 
hazard resulting from contact with both the “hot” 
and neutral wires of the electrical circuit. 
ELECTRICITY IS DANGEROUS. 
EVEN WHEN SAFETY DEVICES ARE 
PRESENT, HANDLE WITH CARE AND USE 
REASONABLE CAUTION. 
 
LET CAUTION PREVAIL 
The CEP temporary power distribution unit is 
designed to be used on a grounded electrical 
supply system. It will not operate when supplied 
from a power source which is not grounded.  
Over-current protection of the proper rating, 
according to the National Electric Code, Article 
240, must be used on the supply circuit feeding 
the temporary power distribution units. 
 
 
 
 
 
 

 

 
 

Reviews: