NEXT SEQUENCE
Select NEXT SEQUENCE if zones should be removed only after the message
ended. When selected, the paging is stopped immediately after the message
ended. Can only be used for MM-2 Messages.
FILTER and trigger list
Select the trigger condition from the list. Enter a string (e.g. GPI) in the text field
FILTER to list only the conditions containing this string.
PAGING
EXISTING
Select EXISTING to select an existing paging from the dropdown menu.
NEW/UPDATE
Select NEW/UPDATE to edit the settings of the paging.
TYPE
Select the paging type from the dropdown.
LABEL
Enter the name of the paging.
PRIORITY
Select the priority of the paging.
ALARM
If the selected paging TYPE = ALARM you can select the alarm type from this
dropdown.
PRECHIME TYPE
If the selected paging TYPE = ANNOUNCEMENT you can select the pre-chime
type from this dropdown.
CHIME TYPE
If the selected paging TYPE = CHIME you can select the chime type from this
dropdown.
MESSAGE NR
If the selected paging TYPE = EVAC Message you can select the message number
from this dropdown.
INPUT CHANNEL
If the selected paging TYPE= ANNOUNCEMENT or TYPE = ALARM (and ALARM =
Extern) you can select the audio input channel for the paging.
DESTINATIONS
Select the zones or groups of the paging.
STATIC
Select a STATIC destination zone pattern for a CONDITION.
DYNAMIC
When selecting a DYNAMIC destination zone pattern, it is only possible to select
one Call Station from the list (no multi selection). For DYNAMIC destinations, the
current selection of the referenced Call Station is used to start the signal when
the condition reaches the state “high” (for a high priority signal).
See Dynamic Destination behavior on a Call Station, page 766.
Notice!
Setting of routing delay
In large PROMATRIX systems the internal routing of pagings can take quite some time. The
property “DPM8000_x.Matrix.Paging.RoutingDelay” allows to delay the activation of the audio
signal source for up to 10000 ms. This allows the system to finalize all routing settings and avoids
the cut off of pre-chimes or other signals.
Keywords in condition list
Keywords can be selected from the condition list to start a signal:
Pagings.VCondition%d.Value where %d is replaced with an ongoing decimal number.
IRIS-Net
PROMATRIX 8000 | en 765
Bosch Security Systems B.V.
User Manual
2017.05 | 3.20 | F.01U.119.956