Element
Description
SPEAKER OUT
System internal description of the zone or line.
ZONE/LINE NAME
Description of the zone or line.
IGNORE
Check this checkbox, if the result of the line measurement should be ignored. A
error of this zone or line will not be indicated in the system. Regular
measurements are carried out anyway.
HINT: If the checkbox is checked a short cut will not be indicated. If the zone is
connected via a line relay, the relay will be deactivated.
GROUND FAULT
This LED lights red, if a ground fault error has occurred.
IMP FAULT
This LED lights red, if the measured impedance is out of the tolerance range.
SHORT FAULT
This LED lights red, if there is a short cut at the zone or line (measured
impedance value below 25% of reference value). In this case the system will not
start calls or alarms in this zone or line.
HINT: If the zone is connected via a line relay, the relay will be deactivated
when there is a short cut (short cut protection for other lines on the same
amplifier).
EOL FAULT
This LED lights red, if a EOL error has occurred.
IRIS-Net
PAVIRO | en 952
Bosch Security Systems B.V.
User Manual
2017.05 | 3.20 | F.01U.119.956