Element
Description
IP ADDRESS
Indicates the IP address of the PVA-4CR12’s Ethernet port (factory setting:
192.168.1.100). Enter the address of the PVA-4CR12 with which you want to
establish on-line communication.
NETWORK MASK
Indicates the Ethernet port’s network mask (factory setting: 255.255.255.0).
GATEWAY ADDRESS
Indicates the standard gateway of the Ethernet port (factory setting:
192.168.1.1).
MAC ADDRESS
Indicates the MAC address of the connected PVA-4CR12 when on-line. The
MAC address of the PVA-4CR12 is also shown on a label on the unit’s rear
panel.
NAME
IRIS-Net internal device name of the PVA-4CR12.
BUZZER
Select ON to indicate a connection failure to a call station (selectable via the
drop down field) via the integrated buzzer of the PVA-4CR12.
SYSTEM LANGUAGE
Select the system language of the PAVIRO system. Please note to update the
call station firmware when selecting Korean or Chinese.
VOICE ALARM STATE
This indicator shows “ACTIVE” if the device is in voice alarm state, else “NOT
ACTIVE”.
RESET
Press the RESET button to deactivate the voice alarm state.
PRIORITY
Select the priority (70–100) of the voice alarm. Select OFF to disable the
voice alarm handling of the device.
AUTO EXIT
Select this checkbox if the voice alarm state should be stopped automatically
after the alarm signal is stopped/muted (e.g. no alarm request present).
DATE/TIME
Date and time of the PVA-4CR12 system clock.
INTERNAL CLOCK
Opens the system clock settings dialog box.
DCF77 SYNCHRONIZATION
Select this option to synchronize the internal clock of the PVA-4CR12 with
the DCF77 signal. Please refer to the manual how to connect an external
DCF77 receiver.
DCF77 SIGNAL STATUS
Indicates the DCF77 signal strength:
–
Green: Signal strength OK
–
Red: Signal strength not OK
NETWORK SYNCHRONIZATION
Select this option to synchronize the internal clock of this PVA-4CR12 with
the internal clock of another PVA-4CR12 connected via Ethernet.
TIME MASTER
Select the PVA-4CR12 (connected via Ethernet) to synchronize the internal
clock with. This drop down can only be used if the NETWORK
SYNCHRONIZATION option is selected.
ENABLE SLAVE CLOCK
Select this checkbox if slave clocks are connected to the PVA-4CR12.
CURRENT SLAVE CLOCK TIME
Set the time for the slave clocks.
FIRMWARE
Indicates the firmware version of the PVA-4CR12 when on-line.
IRIS-Net
PAVIRO | en 914