Property
DPM 8016
System with n DPM 8016 (n
max
= 10)
Signal trigger
200
n * 200
Internal Alarm generators
2
n * 2
Internal Chime generators
2
n * 2
EOL modules (direct topology only)
250
n * 250
EOL modules per amplifier channel
30
Remote control connections (e. g.
IRIS-Net, DPM 8016)
20
n * 20
Number of MM-2 modules per DPM
2
Number of message per MM-2
100
Total length of messages per MM-2
85 minutes
Notice!
Due to security reasons, EVAC systems are not allowed to be connected to public networks or the
internet!
DPM 8016 Paging Manager
The DPM 8016 is the modular, network controlled paging manager of the PROMATRIX 8000 system. Eight audio slots
can be assembled with a combination of audio-input and audio-output cards providing a number of flexible
configuration options. The DPM 8016 provides all the audio processing, supervision and control functions for a
complete PROMATRIX 8000 system. A single DPM 8016 will support up to 16 call stations and 500 paging zones. For
larger systems up to 10 DPM 8016 can be interconnected using a digital audio and control network.
Additional DPM 8016 features:
–
Integrated audio signal processing - 32 x 16 Routing/Mixer Matrix, EQs, Dynamics, Automatic Gain Control
–
Internal supervision with event log - fulfils current requirements of the relevant national and international
standards
–
Various connection possibilities - Ethernet, CAN-Bus, RS-232, CobraNet, GPIOs
DPM 8016 Device
Start by creating an DPM 8016 Device in your IRIS-Net project. Drag an DPM 8016 from the Object Bar’s Devices
category or from the Devices window into the worksheet (see also chapters: Devices and Configurations menu). The
following dialog box appears:
IRIS-Net
PROMATRIX 8000 | en 722
Bosch Security Systems B.V.
User Manual
2017.05 | 3.20 | F.01U.119.956