List of Parameters
Parameters
1-93
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the status of digital outputs.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Inversion using p0748 has been taken into account.
Description:
Setting to invert the signals at the digital outputs.
Note:
DO: Digital output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Description:
Displays the status of analog inputs.
Note:
AI: Analog Input
r0747
CU, digital outputs status / CU DO status
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (NO: T. 19 / NC: T. 18)
High
Low
-
01
DO 1 (NO: T. 21)
High
Low
-
02
DO 2 (NO: T. 24 / NC: T. 23)
High
Low
-
p0748
CU, invert digital outputs / CU DO invert
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (NO: T. 19 / NC: T. 18)
Inverted
Not inverted
-
01
DO 1 (NO: T. 21)
Inverted
Not inverted
-
02
DO 2 (NO: T. 24 / NC: T. 23)
Inverted
Not inverted
-
r0751.0...10
BO: CU analog inputs status word / CU AI status word
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Analog input AI0 wire breakage
Yes
No
-
01
Analog input AI1 wire breakage
Yes
No
-
02
Analog input AI2 wire breakage
Yes
No
-
08
Analog input AI0 no wire breakage
Yes
No
-
09
Analog input AI1 no wire breakage
Yes
No
-
10
Analog input AI2 no wire breakage
Yes
No
-