Parameters
List of Parameters
1-312
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
For a bus off error, the CAN bus is restarted with p8608 = 1 after the cause of the error has been removed.
Value:
0:
Inactive
1:
Start CAN controller
Note:
This parameter is automatically reset to 0 after start.
Description:
Sets the behavior of the CAN node referred to the communications error or equipment fault.
Value:
0:
Pre-operational
1:
No change
2:
Stopped
Index:
[0] = Behavior for communication errors
[1] = Behavior for device faults
Note:
Corresponds to the CANopen object 1029 hex.
Description:
Displays the identifier (client/server and server/client) of the SDO channel.
Index:
[0] = Displays the COB ID from client to server
[1] = Displays the COB ID from server to client
Note:
Corresponds to the CANopen object 1200 hex.
SDO: Service Data Object
p8608
CAN Clear Bus Off Error / Clear bus off err
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0
p8609[0...1]
CAN Error Behaviour / Error behavior
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 2 1
r8610[0...1]
CAN First Server SDO / First server SDO
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-