List of Parameters
Parameters
1-257
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Configuration word for signals and monitoring functions.
Dependency:
Refer to: r2197
Refer to: A07903
Note:
Re bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
Re bit 01:
When the bit is set, load monitoring is only carried out in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
Re bit 03:
When the bit is set, r2197 bit 1 and bit 2 are determined via separate hystereses.
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
Refer to: p2161, r2197, r2199
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
Refer to: r2197, r2198, r2199
Description:
Delay time for the comparison of the speed with the maximum speed.
Dependency:
Refer to: p1082, r1084, r1087, p2162
p2149[0...n]
Monitoring configuration / Monit config
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
- - 1001
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable alarm A07903
Yes
No
8010
01
Load monitoring only in the 1st quadrant
Yes
No
8013
03
n_act > p2155 own hysteresis
Yes
No
8010
p2150[0...n]
Hysteresis speed 3 / n_hysteresis 3
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [rpm]
300.00 [rpm]
2.00 [rpm]
p2151[0...n]
CI: Speed setpoint for messages/signals / n_set for msg
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 1170[0]
p2152[0...n]
Delay for comparison n > n_max / Del n > n_max
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 [ms]
10000 [ms]
200 [ms]
Содержание CU230P-2 CAN
Страница 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Страница 2: ......
Страница 666: ...Index C 666 Siemens AG 2009 All Rights Reserved SINAMICS G120 Control Units CU230P 2 Parameter Manual LH9 11 2009 ...
Страница 667: ......