Parameters
List of Parameters
1-26
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays status word 2.
Caution:
p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
Note:
The following status bits are displayed in r0053:
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
Bit 03: r2197 Bit 8
Bit 04: r2197 Bit 2
Bit 05: r2197 Bit 1
Bit 06: r2197 Bit 4
Bit 07: r2197 Bit 9
Bit 08: r2197 Bit 10
Bit 09: r1199 Bit 2 (negated)
Bit 10: r2349 Bit 10
Bit 11: r2349 Bit 11
Description:
Displays status word 2.
Caution:
p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
Note:
The following status bits are displayed in r0053:
Bit 00: r1239 Bit 8
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
r0053.1...11
CO/BO: Status word 2 / ZSW 2
PM230
PM250, PM260
Access level:
2
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
|n_act| > p1226 (n_standstill)
Yes
No
-
02
|n_act| > p1080 (n_Min)
Yes
No
-
03
I_act >= p2170
Yes
No
-
04
|n_act| > p2155
Yes
No
-
05
|n_act| <= p2155
Yes
No
-
06
|n_act| >= r1119 (n_set)
Yes
No
-
07
Vdc <= p2172
Yes
No
-
08
Vdc > p2172
Yes
No
-
09
Ramp-up/ramp-down completed
Yes
No
-
10
Technology controller output at the lower
limit
Yes
No
-
11
Technology controller output at the upper
limit
Yes
No
-
r0053.0...11
CO/BO: Status word 2 / ZSW 2
PM240
Access level:
2
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DC brake active
Yes
No
-
01
|n_act| > p1226 (n_standstill)
Yes
No
-
02
|n_act| > p1080 (n_Min)
Yes
No
-
03
I_act >= p2170
Yes
No
-
04
|n_act| > p2155
Yes
No
-
05
|n_act| <= p2155
Yes
No
-
06
|n_act| >= r1119 (n_set)
Yes
No
-
07
Vdc <= p2172
Yes
No
-
08
Vdc > p2172
Yes
No
-
09
Ramp-up/ramp-down completed
Yes
No
-
10
Technology controller output at the lower
limit
Yes
No
-
11
Technology controller output at the upper
limit
Yes
No
-
Содержание CU230P-2 CAN
Страница 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Страница 2: ......
Страница 666: ...Index C 666 Siemens AG 2009 All Rights Reserved SINAMICS G120 Control Units CU230P 2 Parameter Manual LH9 11 2009 ...