
List of Parameters
Parameters
1-19
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the smoothed absolute actual current value.
Dependency:
Refer to: r0068
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
Description:
Displays the smoothed actual value of the modulation depth.
Dependency:
Refer to: r0074
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
Description:
Displays the smoothed field-generating actual current.
Dependency:
Refer to: r0076
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
Description:
Displays the smoothed torque-generating actual current.
Dependency:
Refer to: r0078
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
Description:
Displays the smoothed torque actual value.
Dependency:
Refer to: r0080
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The active current actual value is available smoothed (r0031) and unsmoothed (r0080).
r0027
CO: Absolute actual current smoothed / I_act abs val smth
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
r0028
Modulation depth smoothed / Mod_depth smth
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
p2002
Data set:
-
r0029
Current actual value field-generating smoothed / Id_act smooth
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
r0030
Current actual value torque-generating smoothed / Iq_act smooth
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Arms]
Scaling:
p2002
Data set:
-
r0031
Actual torque smoothed / M_act smooth
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Nm]
Scaling:
p2003
Data set:
-
Содержание CU230P-2 CAN
Страница 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Страница 2: ......
Страница 666: ...Index C 666 Siemens AG 2009 All Rights Reserved SINAMICS G120 Control Units CU230P 2 Parameter Manual LH9 11 2009 ...
Страница 667: ......