Parameters
List of Parameters
1-164
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the dead time for non-synchronized bypass.
Note:
This parameter is used to define the changeover time of the contactors. It should not be shorter than the demagne-
tizing time of the motor (p0347). The total changeover time for the bypass is based on the total of p1262 plus the
OFF time for the relevant switch (p1274[x]).
Description:
Sets the delay time to switch back to converter operation for a non-synchronized bypass.
Description:
Sets the delay time for switching to line operation for a non-synchronized bypass.
Description:
Sets the speed threshold to activate the bypass.
Note:
When selecting p1260 = 3 and p1267.1 = 1, the bypass is automatically activated when this speed is reached.
Description:
Sets the signal source for the command to bypass.
p1262[0...n]
Bypass dead time / Bypass t_dead
Access level:
2
Calculated:
p0340 = 1,3
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 [s]
20.000 [s]
1.000 [s]
p1263
Debypass delay time / Debypass t_del
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
300.000 [s]
1.000 [s]
p1264
Bypass delay time / Bypass t_del
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [s]
300.000 [s]
1.000 [s]
p1265
Bypass speed threshold / Bypass n_thresh
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
-
Min Max Factory
setting
0.00 [rpm]
210000.00 [rpm]
1480.00 [rpm]
p1266
BI: Bypass, control command / Bypass command
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
- - 0