Description:
Displays the smoothed actual power factor.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
Significance for the motor: Motor power factor
Significance for the infeed: Power factor at the connection point (p3470, p3471)
Description:
Displays the electrical energy used since the last reset.
Dependency:
Refer to: p0040
Description:
Setting to reset the energy consumption display (r0039).
Procedure: Set p0040 = 0 --> 1.
The display is reset and the parameter is automatically set to zero.
Dependency:
Refer to: r0039
Description:
Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
r0038
Power factor smoothed / Cos phi smooth
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Unit:
-
Scaling:
-
Data set:
-
r0039
Energy consumption / Energy consumption
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[kWh]
Scaling:
-
Data set:
-
p0040
Reset energy consumption display / Energy usage reset
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0
p0045
Smoothing time constant, display values / T_smth display
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [ms]
1000.00 [ms]
4.00 [ms]