Parameters
List of Parameters
1-360
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Display parameter for the output quantity Y = X0 + X1 + X2 + X3 of instance ADD 0 of the adder.
Description:
Setting parameter for the run-time group in which the instance ADD 0 of the adder is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance ADD 0 within the run-time group set in p20096.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source of input quantities X0, X1, X2, X3 of instance ADD 1 of the adder.
Index:
[0] = Input X0
[1] = Input X1
[2] = Input X2
[3] = Input X3
Description:
Display parameter for the output quantity Y = X0 + X1 + X2 + X3 of instance ADD 1 of the adder.
Description:
Setting parameter for the run-time group in which the instance ADD 1 of the adder is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
r20095
CO: ADD 0 output Y / ADD 0 output Y
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
-
Scaling:
PERCENT
Data set:
-
p20096
ADD 0 run-time group / ADD 0 RTG
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
5 9999
9999
p20097
ADD 0 run sequence / ADD 0 RunSeq
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 32000
210
p20098[0...3]
CI: ADD 1 inputs / ADD 1 inputs
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 0
r20099
CO: ADD 1 output Y / ADD 1 output Y
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
-
Scaling:
PERCENT
Data set:
-
p20100
ADD 1 run-time group / ADD 1 RTG
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
5 9999
9999