List of Parameters
Parameters
1-41
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Enter the inductance of a filter connected at the power unit output.
Dependency:
This parameter is automatically preset when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note:
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIE-
MENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside the
commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
Description:
Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency:
This parameter is automatically preset when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note:
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIE-
MENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside the
commissioning phase (p0010 = 0).
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
Description:
Displays the internal resistance of the power unit (IGBT and line resistance).
Note:
For a parallel circuit, the value corresponds to the resistance of a power unit.
Index 0 refers to the first line filter from p0220[0].
Index 1 refers to the optional second line filter from p0220[1].
Description:
Sets the absolute value by which the threshold to initiate the undervoltage fault (F30003) is reduced.
Dependency:
Refer to: p0210, r0296
Refer to: F30003
Notice:
When using a Control Supply Module (CSM) for 24 V supply from the DC link, the minimum continuous DC link volt-
age may not lie below 430 V. DC link voltages in the range 300 ... 430 V are permissible up to a duration of 1 min.
Note:
The resulting shutdown threshold can be read in r0296 and is dependent on the selected rated voltage (p0210) and
the power unit being used.
p0233
Power unit motor reactor / PU mot reactor
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(2), U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [mH]
1000.000 [mH]
0.000 [mH]
p0234
Power unit sine-wave filter capacitance / PU sine filter C
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(2), U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.000 [µF]
1000.000 [µF]
0.000 [µF]
r0238
Power unit internal resistance / PU R_int
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Ohm]
Scaling:
-
Data set:
-
p0278
DC link voltage undervoltage threshold reduction / Vdc V_under red
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
-80 [V]
0 [V]
0 [V]