Parameters
List of Parameters
1-72
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Selects the function for digital input 0.
Value:
0:
No pre-assignment
1:
ON/OFF1
3:
2. OFF2
4:
2. OFF3
9:
2. Acknowledge faults
10:
Jog bit 0
11:
Jog bit 1
12:
Direction reversal
13:
Motorized potentiometer setpoint raise
14:
Motorized potentiometer lower setpoint
15:
Fixed speed setpoint selection Bit 0
16:
Fixed speed setpoint selection Bit 1
17:
Fixed speed setpoint selection Bit 2
18:
Fixed speed setpoint selection Bit 3
26:
Activate emergency operation
27:
Enable technology controller
29:
External fault 1
35:
Command data set selection CDS bit 0
50:
Load monitoring failure detection
Warning:
It is possible to interconnect the digital input with several signal sinks using BICO parameterization without this
parameter providing a message. As a result of the corresponding BICO parameterization, for example, the drive
could undesirably accelerate without this function having been selected in this parameter.
Note:
When changing the function within the selection possibilities, the previously selected interconnection is discon-
nected by resetting the signal sink.
However, the selected function is protected against being changed by BICO parameterization, i.e. the signal sink
must first be enabled using "no pre-assignment" before it can be interconnected again.
p0701[0...n]
Pre-assignment digital input 0 / Pre-assignment DI0
PM230
PM250
PM260
CU230P-2 DP
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
0 50
0