Parameters
List of Parameters
1-258
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the time constant of the PT1 element to smooth the speed / velocity actual value.
The smoothed actual speed/velocity is compared with the threshold values and is only used for messages and sig-
nals.
Dependency:
Refer to: r2169
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2140, r2197
Description:
Sets the switch-in delay time for the signal "comparison value reached" (BO: r2199.1).
Dependency:
Refer to: p2141, p2142, r2199
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 5" (BO: r2198.0)
"|n_act| > speed threshold value 5" (BO: r2198.1)
Dependency:
Refer to: p2150, p2158
Description:
Delay time for the comparison of the speed with the speed threshold value 5 (P2157).
Dependency:
Refer to: p2150, p2157
p2153[0...n]
Speed actual value filter time constant / n_act_filt T
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 [ms]
1000000 [ms]
0 [ms]
p2155[0...n]
Speed threshold 2 / n_thresh val 2
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [rpm]
210000.00 [rpm]
900.00 [rpm]
p2156[0...n]
On delay, comparison value reached / t_on cmpr val rchd
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.0 [ms]
10000.0 [ms]
0.0 [ms]
p2157[0...n]
Speed threshold 5 / n_thresh val 5
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [rpm]
210000.00 [rpm]
900.00 [rpm]
p2158[0...n]
Delay for n_act comparison with speed threshold value 5 / Del compar n_5
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 [ms]
10000 [ms]
10 [ms]